Wire Size for 3.02 Amps

Typical copper wire gauges for 3.02 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 3.02A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

3.02A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.4741V (0.3951%) check_circle OK
50 ft 14 AWG 0.9483V (0.7902%) check_circle OK
75 ft 14 AWG 1.42V (1.19%) check_circle OK
100 ft 14 AWG 1.9V (1.58%) check_circle OK
125 ft 14 AWG 2.37V (1.98%) check_circle OK
150 ft 14 AWG 2.84V (2.37%) check_circle OK
175 ft 14 AWG 3.32V (2.77%) check_circle OK
200 ft 12 AWG 2.39V (1.99%) check_circle OK
250 ft 12 AWG 2.99V (2.49%) check_circle OK
300 ft 12 AWG 3.59V (2.99%) check_circle OK
400 ft 10 AWG 3V (2.5%) check_circle OK
500 ft 8 AWG 2.35V (1.96%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.