Wire Size for 3.26 Amps

Typical copper wire gauges for 3.26 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 3.26A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

3.26A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.5118V (0.4265%) check_circle OK
50 ft 14 AWG 1.02V (0.853%) check_circle OK
75 ft 14 AWG 1.54V (1.28%) check_circle OK
100 ft 14 AWG 2.05V (1.71%) check_circle OK
125 ft 14 AWG 2.56V (2.13%) check_circle OK
150 ft 14 AWG 3.07V (2.56%) check_circle OK
175 ft 14 AWG 3.58V (2.99%) check_circle OK
200 ft 12 AWG 2.58V (2.15%) check_circle OK
250 ft 12 AWG 3.23V (2.69%) check_circle OK
300 ft 10 AWG 2.43V (2.02%) check_circle OK
400 ft 10 AWG 3.23V (2.69%) check_circle OK
500 ft 8 AWG 2.54V (2.11%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.