Wire Size for 3.73 Amps

Typical copper wire gauges for 3.73 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 3.73A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

3.73A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.5856V (0.488%) check_circle OK
50 ft 14 AWG 1.17V (0.976%) check_circle OK
75 ft 14 AWG 1.76V (1.46%) check_circle OK
100 ft 14 AWG 2.34V (1.95%) check_circle OK
125 ft 14 AWG 2.93V (2.44%) check_circle OK
150 ft 14 AWG 3.51V (2.93%) check_circle OK
175 ft 12 AWG 2.58V (2.15%) check_circle OK
200 ft 12 AWG 2.95V (2.46%) check_circle OK
250 ft 10 AWG 2.31V (1.93%) check_circle OK
300 ft 10 AWG 2.78V (2.31%) check_circle OK
400 ft 8 AWG 2.32V (1.93%) check_circle OK
500 ft 8 AWG 2.9V (2.42%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.