Wire Size for 3.82 Amps

Typical copper wire gauges for 3.82 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 3.82A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

3.82A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.5997V (0.4998%) check_circle OK
50 ft 14 AWG 1.2V (0.9996%) check_circle OK
75 ft 14 AWG 1.8V (1.5%) check_circle OK
100 ft 14 AWG 2.4V (2%) check_circle OK
125 ft 14 AWG 3V (2.5%) check_circle OK
150 ft 14 AWG 3.6V (3%) check_circle OK
175 ft 12 AWG 2.65V (2.21%) check_circle OK
200 ft 12 AWG 3.03V (2.52%) check_circle OK
250 ft 10 AWG 2.37V (1.97%) check_circle OK
300 ft 10 AWG 2.84V (2.37%) check_circle OK
400 ft 8 AWG 2.38V (1.98%) check_circle OK
500 ft 8 AWG 2.97V (2.48%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.