Wire Size for 304 Amps
Typical copper and aluminum wire gauges for 304 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.
304A Wire Gauge by Distance
| Distance | Copper Gauge | Aluminum Gauge | V-Drop (Cu) | NEC Status |
|---|---|---|---|---|
| 25 ft | 350 kcmil | 500 kcmil | 0.5578V (0.4649%) | OK |
| 50 ft | 350 kcmil | 500 kcmil | 1.12V (0.9297%) | OK |
| 75 ft | 350 kcmil | 500 kcmil | 1.67V (1.39%) | OK |
| 100 ft | 350 kcmil | 500 kcmil | 2.23V (1.86%) | OK |
| 125 ft | 350 kcmil | 500 kcmil | 2.79V (2.32%) | OK |
| 150 ft | 350 kcmil | 750 kcmil | 3.35V (2.79%) | OK |
| 175 ft | 500 kcmil | 750 kcmil | 2.75V (2.29%) | OK |
| 200 ft | 500 kcmil | 750 kcmil | 3.14V (2.61%) | OK |
| 250 ft | 750 kcmil | no aluminum pick | 2.6V (2.17%) | OK |
| 300 ft | 750 kcmil | no aluminum pick | 3.12V (2.6%) | OK |
| 400 ft | Exceeds available gauges | |||
| 500 ft | Exceeds available gauges | |||
Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.