Wire Size for 31.13 Amps

Typical copper and aluminum wire gauges for 31.13 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

31.13A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 8 AWG 8 AWG 1.21V (1.01%) check_circle OK
50 ft 8 AWG 8 AWG 2.42V (2.02%) check_circle OK
75 ft 6 AWG 6 AWG 2.29V (1.91%) check_circle OK
100 ft 6 AWG 4 AWG 3.06V (2.55%) check_circle OK
125 ft 4 AWG 4 AWG 2.4V (2%) check_circle OK
150 ft 4 AWG 3 AWG 2.88V (2.4%) check_circle OK
175 ft 4 AWG 3 AWG 3.36V (2.8%) check_circle OK
200 ft 3 AWG 2 AWG 3.05V (2.54%) check_circle OK
250 ft 2 AWG 1 AWG 3.02V (2.52%) check_circle OK
300 ft 1 AWG 1/0 AWG 2.88V (2.4%) check_circle OK
400 ft 1/0 AWG 2/0 AWG 3.04V (2.53%) check_circle OK
500 ft 2/0 AWG 3/0 AWG 3.01V (2.51%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.