Wire Size for 336.96 Amps

Typical copper and aluminum wire gauges for 336.96 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

336.96A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 500 kcmil 750 kcmil 0.4347V (0.3622%) check_circle OK
50 ft 500 kcmil 750 kcmil 0.8694V (0.7245%) check_circle OK
75 ft 500 kcmil 750 kcmil 1.3V (1.09%) check_circle OK
100 ft 500 kcmil 750 kcmil 1.74V (1.45%) check_circle OK
125 ft 500 kcmil 750 kcmil 2.17V (1.81%) check_circle OK
150 ft 500 kcmil 750 kcmil 2.61V (2.17%) check_circle OK
175 ft 500 kcmil 750 kcmil 3.04V (2.54%) check_circle OK
200 ft 500 kcmil no aluminum pick 3.48V (2.9%) check_circle OK
250 ft 750 kcmil no aluminum pick 2.88V (2.4%) check_circle OK
300 ft 750 kcmil no aluminum pick 3.46V (2.88%) check_circle OK
400 ftExceeds available gauges
500 ftExceeds available gauges

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.