Wire Size for 34.38 Amps

Typical copper and aluminum wire gauges for 34.38 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

34.38A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 8 AWG 8 AWG 1.34V (1.11%) check_circle OK
50 ft 8 AWG 6 AWG 2.67V (2.23%) check_circle OK
75 ft 6 AWG 6 AWG 2.53V (2.11%) check_circle OK
100 ft 6 AWG 4 AWG 3.38V (2.81%) check_circle OK
125 ft 4 AWG 4 AWG 2.65V (2.21%) check_circle OK
150 ft 4 AWG 3 AWG 3.18V (2.65%) check_circle OK
175 ft 3 AWG 2 AWG 2.95V (2.46%) check_circle OK
200 ft 3 AWG 2 AWG 3.37V (2.81%) check_circle OK
250 ft 2 AWG 1 AWG 3.33V (2.78%) check_circle OK
300 ft 1 AWG 1/0 AWG 3.18V (2.65%) check_circle OK
400 ft 1/0 AWG 2/0 AWG 3.36V (2.8%) check_circle OK
500 ft 2/0 AWG 3/0 AWG 3.32V (2.77%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.