Wire Size for 4.38 Amps

Typical copper wire gauges for 4.38 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 4.38A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

4.38A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.6877V (0.5731%) check_circle OK
50 ft 14 AWG 1.38V (1.15%) check_circle OK
75 ft 14 AWG 2.06V (1.72%) check_circle OK
100 ft 14 AWG 2.75V (2.29%) check_circle OK
125 ft 14 AWG 3.44V (2.87%) check_circle OK
150 ft 12 AWG 2.6V (2.17%) check_circle OK
175 ft 12 AWG 3.04V (2.53%) check_circle OK
200 ft 12 AWG 3.47V (2.89%) check_circle OK
250 ft 10 AWG 2.72V (2.26%) check_circle OK
300 ft 10 AWG 3.26V (2.72%) check_circle OK
400 ft 8 AWG 2.73V (2.27%) check_circle OK
500 ft 8 AWG 3.41V (2.84%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.