Wire Size for 4.95 Amps

Typical copper wire gauges for 4.95 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 4.95A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

4.95A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.7772V (0.6476%) check_circle OK
50 ft 14 AWG 1.55V (1.3%) check_circle OK
75 ft 14 AWG 2.33V (1.94%) check_circle OK
100 ft 14 AWG 3.11V (2.59%) check_circle OK
125 ft 12 AWG 2.45V (2.04%) check_circle OK
150 ft 12 AWG 2.94V (2.45%) check_circle OK
175 ft 12 AWG 3.43V (2.86%) check_circle OK
200 ft 10 AWG 2.46V (2.05%) check_circle OK
250 ft 10 AWG 3.07V (2.56%) check_circle OK
300 ft 8 AWG 2.31V (1.93%) check_circle OK
400 ft 8 AWG 3.08V (2.57%) check_circle OK
500 ft 6 AWG 2.43V (2.03%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.