Wire Size for 42.33 Amps

Typical copper and aluminum wire gauges for 42.33 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

42.33A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 8 AWG 6 AWG 1.65V (1.37%) check_circle OK
50 ft 8 AWG 6 AWG 3.29V (2.74%) check_circle OK
75 ft 6 AWG 4 AWG 3.12V (2.6%) check_circle OK
100 ft 4 AWG 4 AWG 2.61V (2.17%) check_circle OK
125 ft 4 AWG 3 AWG 3.26V (2.72%) check_circle OK
150 ft 3 AWG 2 AWG 3.11V (2.59%) check_circle OK
175 ft 2 AWG 1 AWG 2.87V (2.4%) check_circle OK
200 ft 2 AWG 1 AWG 3.28V (2.74%) check_circle OK
250 ft 1 AWG 1/0 AWG 3.26V (2.72%) check_circle OK
300 ft 1/0 AWG 2/0 AWG 3.1V (2.58%) check_circle OK
400 ft 2/0 AWG 3/0 AWG 3.27V (2.73%) check_circle OK
500 ft 3/0 AWG 4/0 AWG 3.24V (2.7%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.