Wire Size for 5.23 Amps

Typical copper wire gauges for 5.23 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 5.23A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

5.23A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.8211V (0.6843%) check_circle OK
50 ft 14 AWG 1.64V (1.37%) check_circle OK
75 ft 14 AWG 2.46V (2.05%) check_circle OK
100 ft 14 AWG 3.28V (2.74%) check_circle OK
125 ft 12 AWG 2.59V (2.16%) check_circle OK
150 ft 12 AWG 3.11V (2.59%) check_circle OK
175 ft 10 AWG 2.27V (1.89%) check_circle OK
200 ft 10 AWG 2.59V (2.16%) check_circle OK
250 ft 10 AWG 3.24V (2.7%) check_circle OK
300 ft 8 AWG 2.44V (2.03%) check_circle OK
400 ft 8 AWG 3.26V (2.71%) check_circle OK
500 ft 6 AWG 2.57V (2.14%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.