Wire Size for 5.33 Amps

Typical copper wire gauges for 5.33 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 5.33A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

5.33A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.8368V (0.6973%) check_circle OK
50 ft 14 AWG 1.67V (1.39%) check_circle OK
75 ft 14 AWG 2.51V (2.09%) check_circle OK
100 ft 14 AWG 3.35V (2.79%) check_circle OK
125 ft 12 AWG 2.64V (2.2%) check_circle OK
150 ft 12 AWG 3.17V (2.64%) check_circle OK
175 ft 10 AWG 2.31V (1.93%) check_circle OK
200 ft 10 AWG 2.64V (2.2%) check_circle OK
250 ft 10 AWG 3.3V (2.75%) check_circle OK
300 ft 8 AWG 2.49V (2.07%) check_circle OK
400 ft 8 AWG 3.32V (2.76%) check_circle OK
500 ft 6 AWG 2.62V (2.18%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.