Wire Size for 6.82 Amps

Typical copper wire gauges for 6.82 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 6.82A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

6.82A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 1.07V (0.8923%) check_circle OK
50 ft 14 AWG 2.14V (1.78%) check_circle OK
75 ft 14 AWG 3.21V (2.68%) check_circle OK
100 ft 12 AWG 2.7V (2.25%) check_circle OK
125 ft 12 AWG 3.38V (2.81%) check_circle OK
150 ft 10 AWG 2.54V (2.11%) check_circle OK
175 ft 10 AWG 2.96V (2.47%) check_circle OK
200 ft 10 AWG 3.38V (2.82%) check_circle OK
250 ft 8 AWG 2.65V (2.21%) check_circle OK
300 ft 8 AWG 3.18V (2.65%) check_circle OK
400 ft 6 AWG 2.68V (2.23%) check_circle OK
500 ft 6 AWG 3.35V (2.79%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.