Wire Size for 76 Amps

Typical copper and aluminum wire gauges for 76 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

76A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 4 AWG 2 AWG 1.17V (0.9753%) check_circle OK
50 ft 4 AWG 2 AWG 2.34V (1.95%) check_circle OK
75 ft 4 AWG 2 AWG 3.51V (2.93%) check_circle OK
100 ft 2 AWG 1 AWG 2.95V (2.46%) check_circle OK
125 ft 1 AWG 1/0 AWG 2.93V (2.44%) check_circle OK
150 ft 1 AWG 2/0 AWG 3.51V (2.93%) check_circle OK
175 ft 1/0 AWG 2/0 AWG 3.25V (2.7%) check_circle OK
200 ft 2/0 AWG 3/0 AWG 2.94V (2.45%) check_circle OK
250 ft 3/0 AWG 4/0 AWG 2.91V (2.43%) check_circle OK
300 ft 3/0 AWG 300 kcmil 3.49V (2.91%) check_circle OK
400 ft 250 kcmil 500 kcmil 3.13V (2.61%) check_circle OK
500 ft 300 kcmil 500 kcmil 3.26V (2.72%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.