Wire Size for 8.94 Amps

Typical copper wire gauges for 8.94 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 8.94A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

8.94A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 1.4V (1.17%) check_circle OK
50 ft 14 AWG 2.81V (2.34%) check_circle OK
75 ft 12 AWG 2.66V (2.21%) check_circle OK
100 ft 12 AWG 3.54V (2.95%) check_circle OK
125 ft 10 AWG 2.77V (2.31%) check_circle OK
150 ft 10 AWG 3.33V (2.77%) check_circle OK
175 ft 8 AWG 2.43V (2.03%) check_circle OK
200 ft 8 AWG 2.78V (2.32%) check_circle OK
250 ft 8 AWG 3.48V (2.9%) check_circle OK
300 ft 6 AWG 2.63V (2.19%) check_circle OK
400 ft 6 AWG 3.51V (2.93%) check_circle OK
500 ft 4 AWG 2.75V (2.29%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.