How Many Amps Does a 0.167 HP three-phase Motor Draw at 230V?

A 0.167 HP three-phase motor at 230V draws approximately 0.4328 amps per line during normal operation (85% efficiency, PF 0.85). This HP and voltage combination is outside NEC Table 430.250, so there is no code-authoritative LRA multiplier for branch-circuit sizing; refer to the motor nameplate for both running current and startup characteristics.

Common applications for 0.167 HP motors: small pool pumps, light-commercial fans, booster pumps.

0.167 HP three-phase motor at 230V
0.4328 Amps per line running
Calculated running current at the motor terminals at the assumed 85% efficiency and PF 0.85, per line on a balanced three-phase circuit. This is a conversion from the nameplate horsepower using those assumptions, not a measured value; a real meter reading depends on the motor's actual nameplate efficiency, loading, temperature, and motor design.
NEC Table 430.250 FLCoff-table (see nameplate)
Electrical input (HP × 746 ÷ efficiency)146.57 W
0.4328
off-table

Use the running amps for metering and energy calculations. For branch-circuit sizing, AC motors use the NEC Table 430.248 / 430.250 full-load current under NEC 430.6(A)(1); DC motors use the motor nameplate full-load current under NEC 430.6(A)(3), with Table 430.247 as the reference. Three-phase current is shown per line on a balanced circuit.

Formula (three-phase)

I(A) = (HP × 746) ÷ (√3 × VL-L × Eff × PF)

(0.167 × 746) ÷ (√3 × 230 × 0.85 × 0.85) = 124.58 ÷ 287.82 = 0.4328 A per line
  1. Convert HP to watts: 0.167 × 746 = 124.58W
  2. Denominator: √3 × 230 × 0.85 × 0.85 = 1.73 × 230 × 0.85 × 0.85 = 287.82
  3. Result: 124.58 ÷ 287.82 = 0.4328 amps per line

Three-phase current is per line on a balanced circuit. Voltage is line-to-line; the √3 factor comes from the three-phase vector geometry, not a round-trip doubling.

NEC Reference Values

This section lists the Code reference numbers a motor branch circuit is sized from. Final conductor, breaker, disconnect, and overload selection is an install decision a licensed electrician makes against the motor nameplate, the actual install conditions, and the applicable NEC articles, not a decision a conversion page can make for you.

Off-Table: No Code-Anchored Sizing

This combination is off-table because 0.167 HP is not a listed horsepower rating in NEC Table 430.250. The table lists discrete HP values (for three-phase: 1/2, 3/4, 1, 1½, 2, 3, 5, 7½, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, and on up), and 0.167 HP falls between listed values. 230V itself is a standard three-phase voltage in the table.

Per NEC 430.6(A)(1) Exception, when a motor rating falls between listed HP values, the next higher listed HP is used for sizing. For 0.167 HP, that means looking at 0.5 HP in the table.

Because there is no table FLC to anchor the NEC 430.22 conductor and 430.52(C)(1) OCP math, this page deliberately does not show branch-circuit sizing values for this variant. Multiplying the 0.4328 A calculated running current by 125% or 250% would produce numbers that look authoritative but are not what the code requires.

What to do instead:

  • Apply NEC 430.6(A)(1) Exception and size from the next higher listed HP: 0.5 HP three-phase at 230V. The table FLC shown on that page is the Code-authoritative number for your 0.167 HP branch circuit.
  • If this motor is actually single-phase, 0.167 HP single-phase at 230V is in NEC Table 430.248 with an FLC of 2.2 A.
  • Pull the motor nameplate FLC and have a licensed electrician apply the 430.22 (conductor) and 430.52(C)(1) (OCP) rules against that number. NEC 430.6(A)(1) Exception permits using the next-higher listed HP where the motor rating is between table values; your inspector may also accept nameplate-based sizing for unusual HP ratings.

Operating Cost

Motor mechanical output is 124.58 W (0.167 HP × 746). Electrical input at the terminals is higher because no motor is 100% efficient: 124.58 ÷ 0.85 = 146.57 W. At $0.17/kWh, running cost is $0.02/hour or $5.98/month at 8 hours/day. Full breakdown at 146.57 W.

Amps by Motor Efficiency (three-phase)

Motor efficiency directly affects amp draw. A more efficient motor draws less current for the same HP output. Values below are the calculated three-phase running current at 230V per line and PF 0.85:

EfficiencyAmps at 230V (per line)Watts ConsumedWaste Heat
75%0.4906 A166.11 W41.53 W
80%0.4599 A155.73 W31.15 W
85%0.4328 A146.57 W21.99 W
90%0.4088 A138.42 W13.84 W
95%0.3873 A131.14 W6.56 W

Other HP Values at 230V (three-phase)

Running current is the calculated three-phase draw per line at 85% efficiency and 0.85 PF (a conversion from HP under those assumptions, not a measured value). NEC Table FLC is the value from NEC Table 430.250 used for branch-circuit conductor and OCP sizing under NEC 430.6(A)(1). LRA is estimated at 5-7× the NEC table FLC; rows outside the table show n/a because there is no code-authoritative LRA basis for that HP/voltage/phase combination. Row links open each result page in three-phase mode.

HPRunning Amps
(calculated)
NEC Table 430.250 FLCLRA Estimate
(5-7× FLC)
1/8 HP0.324 Aoff-tablen/a
1/6 HP0.4321 Aoff-tablen/a
1/4 HP0.648 Aoff-tablen/a
1/3 HP0.8639 Aoff-tablen/a
1/2 HP1.3 A2.2 A11-15.4 A
3/4 HP1.94 A3.2 A16-22.4 A
1 HP2.59 A4.2 A21-29.4 A
1.5 HP3.89 A6 A30-42 A
2 HP5.18 A6.8 A34-47.6 A
3 HP7.78 A9.6 A48-67.2 A
5 HP12.96 A15.2 A76-106.4 A
7.5 HP19.44 A22 A110-154 A
10 HP25.92 A28 A140-196 A
15 HP38.88 A42 A210-294 A
20 HP51.84 A54 A270-378 A
25 HP64.8 A68 A340-476 A
30 HP77.76 A80 A400-560 A
40 HP103.67 A104 A520-728 A
50 HP129.59 A130 A650-910 A
75 HP194.39 A192 A960-1,344 A

Frequently Asked Questions

At the terminals, a 0.167 HP three-phase motor at 230V draws about 0.4328 amps per line at 85% efficiency and 0.85 power factor. This specific HP and voltage combination is outside NEC Table 430.250, so NEC branch-circuit sizing must come from the motor nameplate and a licensed electrician, not from the calculated value above.
NEC Table 430.52(C)(1) percentages apply to the table full-load current, and this combination is not listed in NEC Table 430.250. The input for the 430.52(C)(1) math here is the motor nameplate FLC, applied by a licensed electrician with the device-type percentage that matches the install (175% dual-element fuse, 250% inverse-time breaker, 300% non-time-delay fuse, 800% instantaneous-trip breaker).
Three-phase motor branches are not served from residential receptacles in the US. Three-phase power is distributed to commercial and industrial services, and a 0.167 HP three-phase motor at 230V needs a dedicated three-phase branch circuit sized by an electrician per NEC 430.22 (conductors) and 430.52(C)(1) (short-circuit / ground-fault protection), against the motor nameplate and install conditions.
Yes. A 0.167 HP three-phase motor at 90% efficiency draws 0.4088 A at the terminals versus 0.4906 A at 75% efficiency. Higher efficiency means lower running amps and lower electrical input wattage for the same mechanical output.
Motors typically run at PF 0.80-0.85 at full load. At no load, PF drops to 0.30-0.40. Low PF means the wire and breaker carry extra reactive current that does no useful mechanical work, which is why NEC motor sizing uses table FLC (which already accounts for typical PF) rather than a simple watts/volts calculation.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.