How Many Amps Does a 1 HP single-phase Motor Draw at 120V?
At 120V, 1 horsepower equals roughly 8.6 amps of running current on a single-phase circuit. One HP is 746 watts of mechanical output, but motors are not 100% efficient, so the electrical draw is higher. Applying V × Eff × PF: 746W ÷ (120 × 0.85 × 0.85) = 746 ÷ 86.7 = 8.6 A.
Where you'll find 1 HP motors: garage door openers, small pool pumps, benchtop tools.
Use this citation when referencing this page.
Use the running amps for metering and energy calculations. For branch-circuit sizing, AC motors use the NEC Table 430.248 / 430.250 full-load current under NEC 430.6(A)(1); DC motors use the motor nameplate full-load current under NEC 430.6(A)(3), with Table 430.247 as the reference. Three-phase current is shown per line on a balanced circuit.
Formula (single-phase)
I(A) = (HP × 746) ÷ (V × Eff × PF)
- Convert HP to watts: 1 × 746 = 746W
- Denominator: 120 × 0.85 × 0.85 = 86.7
- Result: 746 ÷ 86.7 = 8.6 amps
NEC Reference Values
This section lists the Code reference numbers a motor branch circuit is sized from. Final conductor, breaker, disconnect, and overload selection is an install decision a licensed electrician makes against the motor nameplate, the actual install conditions, and the applicable NEC articles, not a decision a conversion page can make for you.
NEC Sizing Base: NEC Table 430.248 FLC
Per NEC 430.6(A)(1), motor branch-circuit conductors, switches, and overcurrent protection are sized from the values in Table 430.248 (single-phase) or Table 430.250 (three-phase), not from the motor nameplate and not from a calculated full-load amps. For a 1 HP single-phase motor at 120V, the table value is 16 A (the 115V column covers 110-120V systems under 430.6(A)(1)).
The 8.6 A shown in the hero is the calculated running current at 85% efficiency and PF 0.85. This is a conversion from the nameplate horsepower under those assumptions, not a measured value; a real meter reading depends on the motor's actual efficiency, loading, temperature, and design. Use this figure for energy and metering estimates, and use 16 A as the reference FLC when an electrician walks through NEC 430 against the nameplate.
NEC 430.22 Conductor Rule (reference formula)
NEC 430.22 requires motor branch-circuit conductor ampacity of at least 125% of the Code sizing FLC. As a reference calculation against the NEC Table 430.248 value: 16 × 1.25 = 20 A. The selected conductor is taken from NEC Table 310.16 at the applicable termination temperature column, with ambient, bundling, and cable-type adjustments applied by the installer. Motor branch-circuit conductors are exempt from the 240.4(D) small-conductor rule via 240.4(G).
NEC 430.52 Overcurrent Protection (code caps)
NEC Table 430.52(C)(1) gives the maximum rating for motor short-circuit and ground-fault protection as a percentage of the Code sizing FLC. The percentage depends on the device type:
| Device Type | Maximum % of Table FLC (430.52(C)(1)) |
|---|---|
| Non-time-delay fuse | 300% |
| Dual-element (time-delay) fuse | 175% |
| Inverse-time circuit breaker | 250% |
| Instantaneous-trip circuit breaker | 800% |
These percentages are maximum caps, not install picks. A real circuit applies the percentage against the Code sizing FLC for the specific device type, rounds up to a standard size per 430.52(C)(1)(a), and is verified against the motor nameplate and the install conditions by the installer. The elevated percentages exist so short-circuit protection does not nuisance-trip on locked-rotor startup inrush.
Locked Rotor (Startup) Current
During the first 2-5 seconds of startup, a squirrel-cage induction motor typically draws 5 to 7 times the NEC Table 430.248 FLC of 16 A (roughly 80 to 112 A). This is why the 430.52(C)(1) percentages above are so much higher than running current: the short-circuit/ground-fault protective device has to ride through locked-rotor inrush without tripping. Actual LRA is set by the motor's NEMA code letter on the nameplate and should be checked there for a real install.
| Current | Amps | Duration |
|---|---|---|
| Calculated running current (meter) | 8.6 A | Continuous at full load |
| NEC Table 430.248 FLC (Code reference) | 16 A | Sizing base, not metered |
| Locked rotor (typical, 5-7×) | 80-112 A | 2-5 seconds |
Operating Cost
Motor mechanical output is 746 W (1 HP × 746). Electrical input at the terminals is higher because no motor is 100% efficient: 746 ÷ 0.85 = 877.65 W. At $0.17/kWh, running cost is $0.15/hour or $35.81/month at 8 hours/day. Full breakdown at 877.65 W.
Amps by Motor Efficiency (single-phase)
Motor efficiency directly affects amp draw. A more efficient motor draws less current for the same HP output. Values below are the calculated single-phase running current at 120V and PF 0.85:
| Efficiency | Amps at 120V | Watts Consumed | Waste Heat |
|---|---|---|---|
| 75% | 9.75 A | 994.67 W | 248.67 W |
| 80% | 9.14 A | 932.5 W | 186.5 W |
| 85% | 8.6 A | 877.65 W | 131.65 W |
| 90% | 8.13 A | 828.89 W | 82.89 W |
| 95% | 7.7 A | 785.26 W | 39.26 W |
Other HP Values at 120V (single-phase)
Running current is the calculated single-phase draw at 85% efficiency and 0.85 PF (a conversion from HP under those assumptions, not a measured value). NEC Table FLC is the value from NEC Table 430.248 used for branch-circuit conductor and OCP sizing under NEC 430.6(A)(1). LRA is estimated at 5-7× the NEC table FLC; rows outside the table show n/a because there is no code-authoritative LRA basis for that HP/voltage/phase combination. Row links open each result page in single-phase mode.
| HP | Running Amps (calculated) | NEC Table 430.248 FLC | LRA Estimate (5-7× FLC) |
|---|---|---|---|
| 1/8 HP | 1.08 A | off-table | n/a |
| 1/6 HP | 1.43 A | 4.4 A | 22-30.8 A |
| 1/4 HP | 2.15 A | 5.8 A | 29-40.6 A |
| 1/3 HP | 2.87 A | 7.2 A | 36-50.4 A |
| 1/2 HP | 4.3 A | 9.8 A | 49-68.6 A |
| 3/4 HP | 6.45 A | 13.8 A | 69-96.6 A |
| 1 HP | 8.6 A | 16 A | 80-112 A |
| 1.5 HP | 12.91 A | 20 A | 100-140 A |
| 2 HP | 17.21 A | 24 A | 120-168 A |
| 3 HP | 25.81 A | 34 A | 170-238 A |
| 5 HP | 43.02 A | 56 A | 280-392 A |
| 7.5 HP | 64.53 A | 80 A | 400-560 A |
| 10 HP | 86.04 A | 100 A | 500-700 A |
| 15 HP | 129.07 A | off-table | n/a |
| 20 HP | 172.09 A | off-table | n/a |
| 25 HP | 215.11 A | off-table | n/a |
| 30 HP | 258.13 A | off-table | n/a |
| 40 HP | 344.18 A | off-table | n/a |
| 50 HP | 430.22 A | off-table | n/a |
| 75 HP | 645.33 A | off-table | n/a |