How Many Amps Does a 3 HP three-phase Motor Draw at 120V?
A 3 HP three-phase motor at 120V draws approximately 14.9 amps per line during normal operation (85% efficiency, PF 0.85). This HP and voltage combination is outside NEC Table 430.250, so there is no code-authoritative LRA multiplier for branch-circuit sizing; refer to the motor nameplate for both running current and startup characteristics.
Common applications for 3 HP motors: small air compressors, dust collectors, shop tools (120V is unusual above 2 HP).
Use this citation when referencing this page.
Use the running amps for metering and energy calculations. For branch-circuit sizing, AC motors use the NEC Table 430.248 / 430.250 full-load current under NEC 430.6(A)(1); DC motors use the motor nameplate full-load current under NEC 430.6(A)(3), with Table 430.247 as the reference. Three-phase current is shown per line on a balanced circuit.
Formula (three-phase)
I(A) = (HP × 746) ÷ (√3 × VL-L × Eff × PF)
- Convert HP to watts: 3 × 746 = 2,238W
- Denominator: √3 × 120 × 0.85 × 0.85 = 1.73 × 120 × 0.85 × 0.85 = 150.17
- Result: 2,238 ÷ 150.17 = 14.9 amps per line
Three-phase current is per line on a balanced circuit. Voltage is line-to-line; the √3 factor comes from the three-phase vector geometry, not a round-trip doubling.
NEC Reference Values
This section lists the Code reference numbers a motor branch circuit is sized from. Final conductor, breaker, disconnect, and overload selection is an install decision a licensed electrician makes against the motor nameplate, the actual install conditions, and the applicable NEC articles, not a decision a conversion page can make for you.
Off-Table: No Code-Anchored Sizing
This combination is off-table because 120V is not a listed three-phase voltage in NEC Table 430.250. The table lists three-phase motors at 200V, 208V, 230V, 460V, and 575V, three-phase power is not typically distributed at 120V, 240V single-leg, 277V, or 400V in the United States. 3 HP is a listed horsepower, but not at this voltage.
Because there is no table FLC to anchor the NEC 430.22 conductor and 430.52(C)(1) OCP math, this page deliberately does not show branch-circuit sizing values for this variant. Multiplying the 14.9 A calculated running current by 125% or 250% would produce numbers that look authoritative but are not what the code requires.
What to do instead:
- Use one of the voltages NEC Table 430.250 actually lists for 3 HP three-phase: 3 HP at 208V 3Φ, 3 HP at 230V 3Φ, 3 HP at 480V 3Φ, 3 HP at 575V 3Φ.
- If this motor is actually single-phase, 3 HP single-phase at 120V is in NEC Table 430.248 with an FLC of 34 A.
- Pull the motor nameplate FLC and have a licensed electrician apply the 430.22 (conductor) and 430.52(C)(1) (OCP) rules against that number. NEC 430.6(A)(1) Exception permits using the next-higher listed HP where the motor rating is between table values; your inspector may also accept nameplate-based sizing for unusual HP ratings.
Operating Cost
Motor mechanical output is 2,238 W (3 HP × 746). Electrical input at the terminals is higher because no motor is 100% efficient: 2,238 ÷ 0.85 = 2,632.94 W. At $0.17/kWh, running cost is $0.45/hour or $107.42/month at 8 hours/day. Full breakdown at 2,632.94 W.
Amps by Motor Efficiency (three-phase)
Motor efficiency directly affects amp draw. A more efficient motor draws less current for the same HP output. Values below are the calculated three-phase running current at 120V per line and PF 0.85:
| Efficiency | Amps at 120V (per line) | Watts Consumed | Waste Heat |
|---|---|---|---|
| 75% | 16.89 A | 2,984 W | 746 W |
| 80% | 15.83 A | 2,797.5 W | 559.5 W |
| 85% | 14.9 A | 2,632.94 W | 394.94 W |
| 90% | 14.08 A | 2,486.67 W | 248.67 W |
| 95% | 13.33 A | 2,355.79 W | 117.79 W |
Other HP Values at 120V (three-phase)
Running current is the calculated three-phase draw per line at 85% efficiency and 0.85 PF (a conversion from HP under those assumptions, not a measured value). NEC Table FLC is the value from NEC Table 430.250 used for branch-circuit conductor and OCP sizing under NEC 430.6(A)(1). LRA is estimated at 5-7× the NEC table FLC; rows outside the table show n/a because there is no code-authoritative LRA basis for that HP/voltage/phase combination. Row links open each result page in three-phase mode.
| HP | Running Amps (calculated) | NEC Table 430.250 FLC | LRA Estimate (5-7× FLC) |
|---|---|---|---|
| 1/8 HP | 0.621 A | off-table | n/a |
| 1/6 HP | 0.8281 A | off-table | n/a |
| 1/4 HP | 1.24 A | off-table | n/a |
| 1/3 HP | 1.66 A | off-table | n/a |
| 1/2 HP | 2.48 A | off-table | n/a |
| 3/4 HP | 3.73 A | off-table | n/a |
| 1 HP | 4.97 A | off-table | n/a |
| 1.5 HP | 7.45 A | off-table | n/a |
| 2 HP | 9.94 A | off-table | n/a |
| 3 HP | 14.9 A | off-table | n/a |
| 5 HP | 24.84 A | off-table | n/a |
| 7.5 HP | 37.26 A | off-table | n/a |
| 10 HP | 49.68 A | off-table | n/a |
| 15 HP | 74.52 A | off-table | n/a |
| 20 HP | 99.35 A | off-table | n/a |
| 25 HP | 124.19 A | off-table | n/a |
| 30 HP | 149.03 A | off-table | n/a |
| 40 HP | 198.71 A | off-table | n/a |
| 50 HP | 248.39 A | off-table | n/a |
| 75 HP | 372.58 A | off-table | n/a |