How Many Amps Is 1.5 kVA at 480V?

A load with an apparent power of 1.5 kVA at 480V draws 1.8 amps per line on a three-phase circuit. 480V is a commercial or industrial panel voltage where three-phase is the dominant interpretation. On single-phase at the same voltage the same apparent power would pull 3.13 amps. At a load power factor of 0.8 the load's real power is 1.2 kW (load-side conversion; a generator or UPS feeding this load has its own separate kW rating set by the manufacturer).

1.5 kVA equals 1.8 amps at 480 volts (three-phase, L-L)
1.8 Amps
Single Phase (480V)3.13 A
1.8

Assumes an AC three-phase line-to-line circuit at the input voltage. kVA is apparent power, so no power factor term is involved.

Formulas

Single Phase

I(A) = (kVA × 1000) ÷ V

(1.5 × 1000) ÷ 480 = 1,500 ÷ 480 = 3.13 A

Three Phase (480V Line-to-Line)

I(A) = (kVA × 1000) ÷ (VL-L × √3)

1,500 ÷ (480 × 1.732) = 1,500 ÷ 831.36 = 1.8 A

Applies to 480Y/277 or 480 delta systems where 480V is the line-to-line voltage.

Single Phase vs Three Phase

The same 1.5 kVA unit draws very different current depending on the phase configuration:

ConfigurationFormulaCurrent at 480V
Single Phase1,500 ÷ 4803.13 A
Three Phase (480V L-L)1,500 ÷ (480 × √3)1.8 A

For this specific case, 1.5 kVA at 480V, three-phase carries about 42.26% less current per line than single-phase at the same voltage. That gap tracks the 1 ÷ √3 factor for L-L three-phase (or 1 ÷ 3 for L-N), which is why three-phase distribution is common at commercial and industrial scale: the same apparent power rides on smaller conductors and smaller breakers (applies to 480Y/277 or 480 delta systems).

Generator & UPS Sizing

Load-Side Real Power by Power Factor

A load with an apparent power of 1.5 kVA draws different amounts of real power depending on the load's own power factor. The table below is a load-side conversion, not a forecast of what a generator or UPS will output for that load: generators and UPS units publish their own independent kW rating set by the engine or inverter design, and that rating is often lower than kVA × the load's PF.

Load TypeLoad PFLoad Real Power (kW)Current at 480V (three-phase, per line)
Resistive (heaters, lights)1.01.5 kW1.8 A per line
Mixed typical0.851.28 kW1.8 A per line
Motors/HVAC0.801.2 kW1.8 A per line
Computers/servers (no PFC)0.650.975 kW1.8 A per line

Note: current draw stays the same across the rows because kVA sets the current, not the load's power factor. PF only affects how much real work (kW) the load does per amp drawn.

Sizing a load against a source. If you are feeding this load from a UPS, generator, or transformer, check the load against both the source's kVA rating AND the source's kW rating. Those are two independent numbers published by the manufacturer. A 10 kVA / 8 kW generator, for example, can supply up to 10 kVA of apparent power AND up to 8 kW of real power, whichever limit is reached first. Do not use the kW figures above as a substitute for the source's published kW rating.

Circuit Sizing: Starting Points

The numbers below are rough order-of-magnitude starting points under typical assumptions (copper conductors, 75°C terminations, short run, no ambient or bundling derates, non-continuous duty). They are not install specs. Actual breaker and wire selection depends on the equipment nameplate, conductor and termination temperature ratings, cable type, run length and voltage-drop target, ambient and bundling conditions, whether the load is continuous, any NEC 430/440 motor or HVAC provisions, and local code.

 Single PhaseThree Phase
Current draw (at full kVA)3.13 A1.8 A
Ballpark branch OCP~15A~15A

For a real install, run the full wire-size calculator with your actual run length, voltage, and drop target, and verify breaker selection against the equipment nameplate and local code.

Energy Cost at Full Load

A load with an apparent power of 1.5 kVA at load PF 0.85 draws 1.28 kW of real power. Running cost at that draw: $0.22/hour at $0.17/kWh (rates last reviewed April 2026), or $52.02/month (8h/day). Full breakdown.

kW Equivalent

1.5 kVA at PF 0.85 = 1.28 kW. See 1.28 kW to amps at 480V.

Other kVA Ratings at 480V

kVAThree Phase Amps (L-L, per line)Single Phase AmpsReal Power (PF 0.8)
1 kVA1.2 A2.08 A0.8 kW
2 kVA2.41 A4.17 A1.6 kW
3 kVA3.61 A6.25 A2.4 kW
5 kVA6.01 A10.42 A4 kW
7.5 kVA9.02 A15.63 A6 kW
10 kVA12.03 A20.83 A8 kW
15 kVA18.04 A31.25 A12 kW
20 kVA24.06 A41.67 A16 kW
25 kVA30.07 A52.08 A20 kW
30 kVA36.08 A62.5 A24 kW
40 kVA48.11 A83.33 A32 kW
50 kVA60.14 A104.17 A40 kW

Frequently Asked Questions

1.5 kVA at 480V is 1.8 amps per line on a three-phase circuit (480Y/277 or 480 delta), or 3.13 amps on single-phase at the same voltage.
Because the current on the output (and therefore the conductor, switchgear, and winding sizing) is set by apparent power, kVA = V×I, regardless of the load's power factor. UPS and generator manufacturers publish a separate kW rating in addition to the kVA rating, set by the inverter or engine design, and it is often lower than the kVA rating. You cannot derive a UPS or generator's kW output from its kVA rating and the load's power factor: the two ratings are independent specs and a load has to fit under each of them when sizing against the source.
kVA is apparent power (V×I), which sets the current on the circuit and the sizing of conductors, breakers, and windings. kW is real power (the portion that does useful work), equal to kVA×load PF. A load with an apparent power of 1.5 kVA at load PF 0.8 draws 1.2 kW of real power. For a source such as a generator or UPS, kVA and kW are two independent manufacturer ratings, not two views of the same spec, and both have to be checked when sizing a load.
A 1.5 kVA unit typically covers essentials (refrigerator, lights, phone and laptop chargers, a furnace blower) but not central AC, electric resistance heat, or an electric range running at the same time. Real capacity depends on simultaneous load, motor starting current, and manual or automatic load shedding.
This is a sizing question, not a conversion question, and there is no single answer from a page like this. Breaker selection depends on the equipment nameplate FLA, whether the load is continuous (NEC 210.19(A) applies the 125% continuous-load rule), conductor ampacity and termination temperature, any NEC 430/440 motor or HVAC provisions, and local code. The current draw on this page is the input to that sizing process, not the output. Verify against the equipment nameplate and a licensed electrician.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.