How Many Amps Is 1.18 kW at 230V?

At 230V, 1.18 kW pulls approximately 6.03 amps on AC single-phase (PF 0.85). This is the case typical for residential water heaters, dryers, ranges, EV chargers, and HVAC equipment. Always verify against the equipment nameplate for actual install sizing.

1.18 kW at 230V, AC single-phase (PF 0.85)
6.03 Amps
1.18 kilowatts at 230V on AC single-phase ≈ 6.03 amps
DC (ideal baseline)5.12 A
6.03

Formulas

DC: kW to Amps

I(A) = 1000 × P(kW) ÷ V(V)

1000 × 1.18 ÷ 230 = 1,178 ÷ 230 = 5.12 A

AC Single Phase (PF = 0.85)

I(A) = 1000 × P(kW) ÷ (PF × V(V))

1,178 ÷ (0.85 × 230) = 1,178 ÷ 195.5 = 6.03 A

Equipment & Circuit Sizing

Breaker Sizing

Breaker ratings are in amps, not watts, so the real install answer depends on the equipment nameplate FLA, whether the load is continuous (NEC 210.19(A) sizes the conductor and OCP at 125% of a continuous load, equivalently 80% of breaker rating), conductor ampacity and temperature rating, ambient and bundling derates, and any motor or HVAC provisions (NEC 430 / 440). At roughly 6.03A on AC single-phase at 230V, the load sits in the bracket between a 15A standard size (non-continuous) and the next size up that covers a continuous load under 210.19(A). The actual install pick depends on whether the load is continuous and the factors above; a conversion page can't pick a single "right" breaker from the amp draw alone.

Energy Cost

1.18 kW costs $0.20/hour at $0.17/kWh (rates last reviewed April 2026). See breakdown.

Power Factor Reference (AC single-phase)

How the line current for 1.18 kW at 230V changes with load power factor, on the same AC single-phase circuit basis the rest of the page uses. DC has no power factor; PF 1.0 represents resistive AC loads.

Load TypePF1.18 kW at 230V (AC single-phase)
Resistive (heaters, incandescent)15.12 A
Fluorescent lamps0.955.39 A
LED lighting0.95.69 A
Synchronous motors0.95.69 A
Typical mixed loads0.856.03 A
Induction motors (full load)0.86.4 A
Computers (without PFC)0.657.88 A
Induction motors (no load)0.3514.63 A

AC Conversion Comparison

On DC, 1.18kW at 230V draws 5.12A. AC single-phase at PF 0.85 pulls 6.03A because reactive current is added on top of the real power.

Circuit TypeFormulaResult
DC1,178 ÷ 2305.12 A
AC Single Phase (PF 0.85)1,178 ÷ (0.85 × 230)6.03 A

Other kW Values at 230V

kWAC 1-Phase PF 0.85DC Amps PF 1.0 baseline
0.5 kW2.56 A2.17 A
0.75 kW3.84 A3.26 A
1 kW5.12 A4.35 A
1.5 kW7.67 A6.52 A
2 kW10.23 A8.7 A
2.5 kW12.79 A10.87 A
3 kW15.35 A13.04 A
3.5 kW17.9 A15.22 A
4 kW20.46 A17.39 A
5 kW25.58 A21.74 A
6 kW30.69 A26.09 A
7.5 kW38.36 A32.61 A
8 kW40.92 A34.78 A
10 kW51.15 A43.48 A
12 kW61.38 A52.17 A

Frequently Asked Questions

1.18 kW at 230V draws about 6.03 amps on an AC single-phase circuit at PF 0.85. Alternate cases at the same voltage: 5.12A on DC.
1.18 kW can be either. Residential loads up to about 5 kW (water heaters, dryers, EV chargers at 240V) are usually single-phase; commercial panels often serve the same load three-phase at 208V or 480V.
1.18 kW equals 1,178 watts. Multiply kilowatts by 1000.
DC: Amps = (kW × 1000) ÷ Volts. AC single-phase: Amps = (kW × 1000) ÷ (Volts × PF). AC three-phase: Amps = (kW × 1000) ÷ (VoltsL-L × √3 × PF).
At 230V, a 1.18 kW EVSE draws about 6.03A on AC single-phase at PF 0.85. This is Level 2 territory, the standard residential (240V) or commercial (208V) AC charging tier covered by NEC Article 625. Home Level 2 units are typically 7.2 to 19.2 kW (30-80A); anything above that is usually commercial hardware or DC fast charging.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.