How Many Amps Is 18 kW at 400V?

At 400V, 18 kW pulls approximately 30.57 amps on AC three-phase (PF 0.85). This is the case typical for commercial HVAC, industrial motors, rooftop units, and three-phase panel loads. Always verify against the equipment nameplate for actual install sizing.

18 kW at 400V, AC three-phase (PF 0.85)
30.57 Amps
18 kilowatts at 400V on AC three-phase ≈ 30.57 amps
AC Single Phase (PF 0.85)52.94 A
DC (ideal baseline)45 A
30.57

Formulas

DC: kW to Amps

I(A) = 1000 × P(kW) ÷ V(V)

1000 × 18 ÷ 400 = 18,000 ÷ 400 = 45 A

AC Single Phase (PF = 0.85)

I(A) = 1000 × P(kW) ÷ (PF × V(V))

18,000 ÷ (0.85 × 400) = 18,000 ÷ 340 = 52.94 A

AC Three Phase (PF = 0.85)

I(A) = 1000 × P(kW) ÷ (√3 × PF × VL-L), where VL-L is the line-to-line voltage

18,000 ÷ (1.732 × 0.85 × 400) = 18,000 ÷ 588.88 = 30.57 A

Equipment & Circuit Sizing

Breaker Sizing

Breaker ratings are in amps, not watts, so the real install answer depends on the equipment nameplate FLA, whether the load is continuous (NEC 210.19(A) sizes the conductor and OCP at 125% of a continuous load, equivalently 80% of breaker rating), conductor ampacity and temperature rating, ambient and bundling derates, and any motor or HVAC provisions (NEC 430 / 440). At roughly 30.57A on AC three-phase at 400V, the load sits in the bracket between a 35A standard size (non-continuous) and the next size up that covers a continuous load under 210.19(A) (around 40A). The actual install pick depends on whether the load is continuous and the factors above; a conversion page can't pick a single "right" breaker from the amp draw alone.

Energy Cost

18 kW costs $3.06/hour at $0.17/kWh (rates last reviewed April 2026). See breakdown.

Power Factor Reference (AC three-phase)

How the line current for 18 kW at 400V changes with load power factor, on the same AC three-phase circuit basis the rest of the page uses. DC has no power factor; PF 1.0 represents resistive AC loads.

Load TypePF18 kW at 400V (AC three-phase)
Resistive (heaters, incandescent)125.98 A
Fluorescent lamps0.9527.35 A
LED lighting0.928.87 A
Synchronous motors0.928.87 A
Typical mixed loads0.8530.57 A
Induction motors (full load)0.832.48 A
Computers (without PFC)0.6539.97 A
Induction motors (no load)0.3574.23 A

AC Conversion Comparison

On DC, 18kW at 400V draws 45A. AC single-phase at PF 0.85 pulls 52.94A because reactive current is added on top of the real power. Three-phase at the same voltage needs only 30.57A per line since the same 18kW is shared across three conductors instead of one.

Circuit TypeFormulaResult
DC18,000 ÷ 40045 A
AC Single Phase (PF 0.85)18,000 ÷ (0.85 × 400)52.94 A
AC Three Phase (PF 0.85)18,000 ÷ (1.732 × 0.85 × 400)30.57 A

Other kW Values at 400V

kWAC 3-Phase per line, PF 0.85AC 1-Phase PF 0.85
3 kW5.09 A8.82 A
3.5 kW5.94 A10.29 A
4 kW6.79 A11.76 A
5 kW8.49 A14.71 A
6 kW10.19 A17.65 A
7.5 kW12.74 A22.06 A
8 kW13.58 A23.53 A
10 kW16.98 A29.41 A
12 kW20.38 A35.29 A
15 kW25.47 A44.12 A
18 kW30.57 A52.94 A
20 kW33.96 A58.82 A
22 kW37.36 A64.71 A
25 kW42.45 A73.53 A
30 kW50.94 A88.24 A

Frequently Asked Questions

18 kW at 400V draws about 30.57 amps on an AC three-phase circuit at PF 0.85. Alternate cases at the same voltage: 45A on DC, 52.94A on AC single-phase.
This is a sizing question, not a conversion question, and there is no single correct answer from a page like this. Breaker selection depends on the equipment nameplate FLA, whether the load is continuous (NEC 210.19(A) applies the 125% continuous-load rule), the conductor ampacity and temperature rating, any NEC 430/440 motor or HVAC provisions, and local code interpretation. Use the nameplate and a licensed electrician for the real install value; use this page only for the current-draw estimate that feeds into that process.
18 kW costs $3.06 per hour at $0.17/kWh (US residential average, last reviewed April 2026). At 8 hours/day that is $734.40 per month.
Industrial equipment operates at higher power levels. 18 kW is easier to express than 18,000W. The math is identical, just scaled by 1000.
Three-phase at 400V draws 30.57A per line versus 52.94A single-phase. Less current per conductor means smaller wire and lower I²R losses.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.