How Many Amps Is 2.7 kW at 480V?

2.7 kW at 480V draws about 3.82 amps on an AC three-phase circuit at PF 0.85, typical for commercial HVAC, industrial motors, rooftop units, and three-phase panel loads. Actual current varies with equipment power factor and duty cycle.

2.7 kW at 480V, AC three-phase (PF 0.85)
3.82 Amps
2.7 kilowatts at 480V on AC three-phase ≈ 3.82 amps
AC Single Phase (PF 0.85)6.62 A
DC (ideal baseline)5.63 A
3.82

Formulas

DC: kW to Amps

I(A) = 1000 × P(kW) ÷ V(V)

1000 × 2.7 ÷ 480 = 2,700 ÷ 480 = 5.63 A

AC Single Phase (PF = 0.85)

I(A) = 1000 × P(kW) ÷ (PF × V(V))

2,700 ÷ (0.85 × 480) = 2,700 ÷ 408 = 6.62 A

AC Three Phase (PF = 0.85)

I(A) = 1000 × P(kW) ÷ (√3 × PF × VL-L), where VL-L is the line-to-line voltage

2,700 ÷ (1.732 × 0.85 × 480) = 2,700 ÷ 706.66 = 3.82 A

Equipment & Circuit Sizing

Breaker Sizing

Breaker ratings are in amps, not watts, so the real install answer depends on the equipment nameplate FLA, whether the load is continuous (NEC 210.19(A) sizes the conductor and OCP at 125% of a continuous load, equivalently 80% of breaker rating), conductor ampacity and temperature rating, ambient and bundling derates, and any motor or HVAC provisions (NEC 430 / 440). At roughly 3.82A on AC three-phase at 480V, the load sits in the bracket between a 15A standard size (non-continuous) and the next size up that covers a continuous load under 210.19(A). The actual install pick depends on whether the load is continuous and the factors above; a conversion page can't pick a single "right" breaker from the amp draw alone.

Energy Cost

2.7 kW costs $0.46/hour at $0.17/kWh (rates last reviewed April 2026). See breakdown.

Power Factor Reference (AC three-phase)

How the line current for 2.7 kW at 480V changes with load power factor, on the same AC three-phase circuit basis the rest of the page uses. DC has no power factor; PF 1.0 represents resistive AC loads.

Load TypePF2.7 kW at 480V (AC three-phase)
Resistive (heaters, incandescent)13.25 A
Fluorescent lamps0.953.42 A
LED lighting0.93.61 A
Synchronous motors0.93.61 A
Typical mixed loads0.853.82 A
Induction motors (full load)0.84.06 A
Computers (without PFC)0.655 A
Induction motors (no load)0.359.28 A

AC Conversion Comparison

On DC, 2.7kW at 480V draws 5.63A. AC single-phase at PF 0.85 pulls 6.62A because reactive current is added on top of the real power. Three-phase at the same voltage needs only 3.82A per line since the same 2.7kW is shared across three conductors instead of one.

Circuit TypeFormulaResult
DC2,700 ÷ 4805.63 A
AC Single Phase (PF 0.85)2,700 ÷ (0.85 × 480)6.62 A
AC Three Phase (PF 0.85)2,700 ÷ (1.732 × 0.85 × 480)3.82 A

Other kW Values at 480V

kWAC 3-Phase per line, PF 0.85AC 1-Phase PF 0.85
0.5 kW0.7075 A1.23 A
0.75 kW1.06 A1.84 A
1 kW1.42 A2.45 A
1.5 kW2.12 A3.68 A
2 kW2.83 A4.9 A
2.5 kW3.54 A6.13 A
3 kW4.25 A7.35 A
3.5 kW4.95 A8.58 A
4 kW5.66 A9.8 A
5 kW7.08 A12.25 A
6 kW8.49 A14.71 A
7.5 kW10.61 A18.38 A
8 kW11.32 A19.61 A
10 kW14.15 A24.51 A
12 kW16.98 A29.41 A

Frequently Asked Questions

2.7 kW at 480V draws about 3.82 amps on an AC three-phase circuit at PF 0.85. Alternate cases at the same voltage: 5.63A on DC, 6.62A on AC single-phase.
2.7 kW can be either. Residential loads up to about 5 kW (water heaters, dryers, EV chargers at 240V) are usually single-phase; commercial panels often serve the same load three-phase at 208V or 480V.
Industrial equipment operates at higher power levels. 2.7 kW is easier to express than 2,700W. The math is identical, just scaled by 1000.
DC: Amps = (kW × 1000) ÷ Volts. AC single-phase: Amps = (kW × 1000) ÷ (Volts × PF). AC three-phase: Amps = (kW × 1000) ÷ (VoltsL-L × √3 × PF).
480V is commercial/industrial panel voltage, not a typical AC EVSE feed to a vehicle. On three-phase 480V, 2.7 kW works out to about 3.82A per line (three-phase at PF 0.85). In practice, 400-480V three-phase is usually the AC input to a DC fast charger (50-350 kW CCS/NACS stations like Tesla Superchargers), which rectifies to DC and delivers that directly to the vehicle, rather than an AC EVSE connector. A 2.7 kW figure at 480V is most likely the AC feed to a smaller commercial cabinet or the control-side input of a larger DC fast charger, not an at-the-car AC current.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.