How Many Amps Is 21.16 kW at 480V?

At 480V, 21.16 kW pulls approximately 29.95 amps on AC three-phase (PF 0.85). This is the case typical for commercial HVAC, industrial motors, rooftop units, and three-phase panel loads. Always verify against the equipment nameplate for actual install sizing.

21.16 kW at 480V, AC three-phase (PF 0.85)
29.95 Amps
21.16 kilowatts at 480V on AC three-phase ≈ 29.95 amps
AC Single Phase (PF 0.85)51.87 A
DC (ideal baseline)44.09 A
29.95

Formulas

DC: kW to Amps

I(A) = 1000 × P(kW) ÷ V(V)

1000 × 21.16 ÷ 480 = 21,163 ÷ 480 = 44.09 A

AC Single Phase (PF = 0.85)

I(A) = 1000 × P(kW) ÷ (PF × V(V))

21,163 ÷ (0.85 × 480) = 21,163 ÷ 408 = 51.87 A

AC Three Phase (PF = 0.85)

I(A) = 1000 × P(kW) ÷ (√3 × PF × VL-L), where VL-L is the line-to-line voltage

21,163 ÷ (1.732 × 0.85 × 480) = 21,163 ÷ 706.66 = 29.95 A

Equipment & Circuit Sizing

Breaker Sizing

Breaker ratings are in amps, not watts, so the real install answer depends on the equipment nameplate FLA, whether the load is continuous (NEC 210.19(A) sizes the conductor and OCP at 125% of a continuous load, equivalently 80% of breaker rating), conductor ampacity and temperature rating, ambient and bundling derates, and any motor or HVAC provisions (NEC 430 / 440). At roughly 29.95A on AC three-phase at 480V, the load sits in the bracket between a 30A standard size (non-continuous) and the next size up that covers a continuous load under 210.19(A) (around 40A). The actual install pick depends on whether the load is continuous and the factors above; a conversion page can't pick a single "right" breaker from the amp draw alone.

Energy Cost

21.16 kW costs $3.60/hour at $0.17/kWh (rates last reviewed April 2026). See breakdown.

Power Factor Reference (AC three-phase)

How the line current for 21.16 kW at 480V changes with load power factor, on the same AC three-phase circuit basis the rest of the page uses. DC has no power factor; PF 1.0 represents resistive AC loads.

Load TypePF21.16 kW at 480V (AC three-phase)
Resistive (heaters, incandescent)125.46 A
Fluorescent lamps0.9526.79 A
LED lighting0.928.28 A
Synchronous motors0.928.28 A
Typical mixed loads0.8529.95 A
Induction motors (full load)0.831.82 A
Computers (without PFC)0.6539.16 A
Induction motors (no load)0.3572.73 A

AC Conversion Comparison

On DC, 21.16kW at 480V draws 44.09A. AC single-phase at PF 0.85 pulls 51.87A because reactive current is added on top of the real power. Three-phase at the same voltage needs only 29.95A per line since the same 21.16kW is shared across three conductors instead of one.

Circuit TypeFormulaResult
DC21,163 ÷ 48044.09 A
AC Single Phase (PF 0.85)21,163 ÷ (0.85 × 480)51.87 A
AC Three Phase (PF 0.85)21,163 ÷ (1.732 × 0.85 × 480)29.95 A

Other kW Values at 480V

kWAC 3-Phase per line, PF 0.85AC 1-Phase PF 0.85
3.5 kW4.95 A8.58 A
4 kW5.66 A9.8 A
5 kW7.08 A12.25 A
6 kW8.49 A14.71 A
7.5 kW10.61 A18.38 A
8 kW11.32 A19.61 A
10 kW14.15 A24.51 A
12 kW16.98 A29.41 A
15 kW21.23 A36.76 A
18 kW25.47 A44.12 A
20 kW28.3 A49.02 A
22 kW31.13 A53.92 A
25 kW35.38 A61.27 A
30 kW42.45 A73.53 A
35 kW49.53 A85.78 A

Same kW, Other Voltages

Each destination page leads with the interpretation most common for that voltage, so the amps shown below use the same basis as the page you'd land on: single-phase for residential voltages, three-phase for commercial/industrial panel voltages, DC for low-voltage.

Frequently Asked Questions

21.16 kW at 480V draws about 29.95 amps on an AC three-phase circuit at PF 0.85. Alternate cases at the same voltage: 44.09A on DC, 51.87A on AC single-phase.
21.16 kW is typically three-phase in commercial and industrial settings.
Three-phase at 480V draws 29.95A per line versus 51.87A single-phase. Less current per conductor means smaller wire and lower I²R losses.
This is a sizing question, not a conversion question, and there is no single correct answer from a page like this. Breaker selection depends on the equipment nameplate FLA, whether the load is continuous (NEC 210.19(A) applies the 125% continuous-load rule), the conductor ampacity and temperature rating, any NEC 430/440 motor or HVAC provisions, and local code interpretation. Use the nameplate and a licensed electrician for the real install value; use this page only for the current-draw estimate that feeds into that process.
480V is commercial/industrial panel voltage, not a typical AC EVSE feed to a vehicle. On three-phase 480V, 21.16 kW works out to about 29.95A per line (three-phase at PF 0.85). In practice, 400-480V three-phase is usually the AC input to a DC fast charger (50-350 kW CCS/NACS stations like Tesla Superchargers), which rectifies to DC and delivers that directly to the vehicle, rather than an AC EVSE connector. A 21.16 kW figure at 480V is most likely the AC feed to a smaller commercial cabinet or the control-side input of a larger DC fast charger, not an at-the-car AC current.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.