How Many Amps Is 24 kW at 240V?

24 kW at 240V draws about 117.65 amps on an AC single-phase circuit at PF 0.85, typical for residential water heaters, dryers, ranges, EV chargers, and HVAC equipment. Actual current varies with equipment power factor and duty cycle.

24 kW at 240V, AC single-phase (PF 0.85)
117.65 Amps
24 kilowatts at 240V on AC single-phase ≈ 117.65 amps
DC (ideal baseline)100 A
117.65

Formulas

DC: kW to Amps

I(A) = 1000 × P(kW) ÷ V(V)

1000 × 24 ÷ 240 = 24,000 ÷ 240 = 100 A

AC Single Phase (PF = 0.85)

I(A) = 1000 × P(kW) ÷ (PF × V(V))

24,000 ÷ (0.85 × 240) = 24,000 ÷ 204 = 117.65 A

Equipment & Circuit Sizing

Breaker Sizing

Breaker ratings are in amps, not watts, so the real install answer depends on the equipment nameplate FLA, whether the load is continuous (NEC 210.19(A) sizes the conductor and OCP at 125% of a continuous load, equivalently 80% of breaker rating), conductor ampacity and temperature rating, ambient and bundling derates, and any motor or HVAC provisions (NEC 430 / 440). At roughly 117.65A on AC single-phase at 240V, the load sits in the bracket between a 125A standard size (non-continuous) and the next size up that covers a continuous load under 210.19(A) (around 150A). The actual install pick depends on whether the load is continuous and the factors above; a conversion page can't pick a single "right" breaker from the amp draw alone.

Energy Cost

24 kW costs $4.08/hour at $0.17/kWh (rates last reviewed April 2026). See breakdown.

Power Factor Reference (AC single-phase)

How the line current for 24 kW at 240V changes with load power factor, on the same AC single-phase circuit basis the rest of the page uses. DC has no power factor; PF 1.0 represents resistive AC loads.

Load TypePF24 kW at 240V (AC single-phase)
Resistive (heaters, incandescent)1100 A
Fluorescent lamps0.95105.26 A
LED lighting0.9111.11 A
Synchronous motors0.9111.11 A
Typical mixed loads0.85117.65 A
Induction motors (full load)0.8125 A
Computers (without PFC)0.65153.85 A
Induction motors (no load)0.35285.71 A

AC Conversion Comparison

On DC, 24kW at 240V draws 100A. AC single-phase at PF 0.85 pulls 117.65A because reactive current is added on top of the real power.

Circuit TypeFormulaResult
DC24,000 ÷ 240100 A
AC Single Phase (PF 0.85)24,000 ÷ (0.85 × 240)117.65 A

Other kW Values at 240V

kWAC 1-Phase PF 0.85DC Amps PF 1.0 baseline
4 kW19.61 A16.67 A
5 kW24.51 A20.83 A
6 kW29.41 A25 A
7.5 kW36.76 A31.25 A
8 kW39.22 A33.33 A
10 kW49.02 A41.67 A
12 kW58.82 A50 A
15 kW73.53 A62.5 A
18 kW88.24 A75 A
20 kW98.04 A83.33 A
22 kW107.84 A91.67 A
25 kW122.55 A104.17 A
30 kW147.06 A125 A
35 kW171.57 A145.83 A
40 kW196.08 A166.67 A

Same kW, Other Voltages

Each destination page leads with the interpretation most common for that voltage, so the amps shown below use the same basis as the page you'd land on: single-phase for residential voltages, three-phase for commercial/industrial panel voltages, DC for low-voltage.

Frequently Asked Questions

24 kW at 240V draws about 117.65 amps on an AC single-phase circuit at PF 0.85. Alternate cases at the same voltage: 100A on DC.
On AC single-phase, current scales inversely with power factor. At PF 1.0 (pure resistive, like a heater), 24 kW at 240V draws 100A. At PF 0.80 (typical induction motor), the same real power draws 125A. The extra current is reactive and does no real work, but still flows through the wire and the breaker.
24 kW equals 24,000 watts. Multiply kilowatts by 1000.
24 kW is typically three-phase in commercial and industrial settings.
Industrial equipment operates at higher power levels. 24 kW is easier to express than 24,000W. The math is identical, just scaled by 1000.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.