How Many Amps Is 3.39 kW at 208V?

At 208V, 3.39 kW pulls approximately 11.06 amps on AC three-phase (PF 0.85). This is the case typical for commercial HVAC, industrial motors, rooftop units, and three-phase panel loads. Always verify against the equipment nameplate for actual install sizing.

3.39 kW at 208V, AC three-phase (PF 0.85)
11.06 Amps
3.39 kilowatts at 208V on AC three-phase ≈ 11.06 amps
AC Single Phase (PF 0.85)19.15 A
DC (ideal baseline)16.28 A
11.06

Formulas

DC: kW to Amps

I(A) = 1000 × P(kW) ÷ V(V)

1000 × 3.39 ÷ 208 = 3,386 ÷ 208 = 16.28 A

AC Single Phase (PF = 0.85)

I(A) = 1000 × P(kW) ÷ (PF × V(V))

3,386 ÷ (0.85 × 208) = 3,386 ÷ 176.8 = 19.15 A

AC Three Phase (PF = 0.85)

I(A) = 1000 × P(kW) ÷ (√3 × PF × VL-L), where VL-L is the line-to-line voltage

3,386 ÷ (1.732 × 0.85 × 208) = 3,386 ÷ 306.22 = 11.06 A

Equipment & Circuit Sizing

Breaker Sizing

Breaker ratings are in amps, not watts, so the real install answer depends on the equipment nameplate FLA, whether the load is continuous (NEC 210.19(A) sizes the conductor and OCP at 125% of a continuous load, equivalently 80% of breaker rating), conductor ampacity and temperature rating, ambient and bundling derates, and any motor or HVAC provisions (NEC 430 / 440). At roughly 11.06A on AC three-phase at 208V, the load sits in the bracket between a 15A standard size (non-continuous) and the next size up that covers a continuous load under 210.19(A). The actual install pick depends on whether the load is continuous and the factors above; a conversion page can't pick a single "right" breaker from the amp draw alone.

Energy Cost

3.39 kW costs $0.58/hour at $0.17/kWh (rates last reviewed April 2026). See breakdown.

Power Factor Reference (AC three-phase)

How the line current for 3.39 kW at 208V changes with load power factor, on the same AC three-phase circuit basis the rest of the page uses. DC has no power factor; PF 1.0 represents resistive AC loads.

Load TypePF3.39 kW at 208V (AC three-phase)
Resistive (heaters, incandescent)19.4 A
Fluorescent lamps0.959.89 A
LED lighting0.910.44 A
Synchronous motors0.910.44 A
Typical mixed loads0.8511.06 A
Induction motors (full load)0.811.75 A
Computers (without PFC)0.6514.46 A
Induction motors (no load)0.3526.85 A

AC Conversion Comparison

On DC, 3.39kW at 208V draws 16.28A. AC single-phase at PF 0.85 pulls 19.15A because reactive current is added on top of the real power. Three-phase at the same voltage needs only 11.06A per line since the same 3.39kW is shared across three conductors instead of one.

Circuit TypeFormulaResult
DC3,386 ÷ 20816.28 A
AC Single Phase (PF 0.85)3,386 ÷ (0.85 × 208)19.15 A
AC Three Phase (PF 0.85)3,386 ÷ (1.732 × 0.85 × 208)11.06 A

Other kW Values at 208V

kWAC 3-Phase per line, PF 0.85AC 1-Phase PF 0.85
0.5 kW1.63 A2.83 A
0.75 kW2.45 A4.24 A
1 kW3.27 A5.66 A
1.5 kW4.9 A8.48 A
2 kW6.53 A11.31 A
2.5 kW8.16 A14.14 A
3 kW9.8 A16.97 A
3.5 kW11.43 A19.8 A
4 kW13.06 A22.62 A
5 kW16.33 A28.28 A
6 kW19.59 A33.94 A
7.5 kW24.49 A42.42 A
8 kW26.12 A45.25 A
10 kW32.66 A56.56 A
12 kW39.19 A67.87 A

Frequently Asked Questions

3.39 kW at 208V draws about 11.06 amps on an AC three-phase circuit at PF 0.85. Alternate cases at the same voltage: 16.28A on DC, 19.15A on AC single-phase.
3.39 kW equals 3,386 watts. Multiply kilowatts by 1000.
This is a sizing question, not a conversion question, and there is no single correct answer from a page like this. Breaker selection depends on the equipment nameplate FLA, whether the load is continuous (NEC 210.19(A) applies the 125% continuous-load rule), the conductor ampacity and temperature rating, any NEC 430/440 motor or HVAC provisions, and local code interpretation. Use the nameplate and a licensed electrician for the real install value; use this page only for the current-draw estimate that feeds into that process.
3.39 kW can be either. Residential loads up to about 5 kW (water heaters, dryers, EV chargers at 240V) are usually single-phase; commercial panels often serve the same load three-phase at 208V or 480V.
Three-phase at 208V draws 11.06A per line versus 19.15A single-phase. Less current per conductor means smaller wire and lower I²R losses.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.