How Many Watts Is 100 VA?

A load with an apparent power of 100 VA draws 85 watts of real power at PF 0.85. For UPS and power-supply sizing, this tells you the load's watt draw, not the source's watt output: a UPS has its own manufacturer-set watt rating that is independent of its VA rating and must be checked separately on the spec sheet.

100 VA equals 85 watts (PF 0.85)
85 Watts
Resistive estimate (PF 1.0)100 W
Motor mix estimate (PF 0.80)80 W
Computer load estimate (PF 0.65)65 W
85

Formula

Watts = VA × PF

100 × 0.85 = 85 W

Watts by Power Factor

Load TypePF100 VA =
Resistive (heaters, incandescent)1100 W
Fluorescent lamps0.9595 W
LED lighting0.990 W
Synchronous motors0.990 W
Typical mixed loads0.8585 W
Induction motors (full load)0.880 W
Computers (without PFC)0.6565 W
Induction motors (no load)0.3535 W

Using This Figure for UPS & Power Supply Sizing

Important framing. The 85W figure above is the real power a 100 VA load draws at PF 0.85. It is not the watt output of a 100 VA UPS. UPS units publish two independent ratings set by the manufacturer: a VA rating and a watt rating. A 100 VA UPS from one vendor may be rated for well under 85W continuous real power, and another 100 VA UPS may be rated for the full 100W. You cannot tell from the VA rating alone. Always check the UPS's watt rating on the manufacturer's spec sheet, and size the load to fit under both the VA rating and the watt rating.

Does Your Load Fit Under a 100 VA UPS?

Two checks, both required:

  1. Apparent power: add up the VA of all connected equipment. The total must not exceed the UPS's VA rating (100 VA in this example).
  2. Real power: add up the watts of all connected equipment. The total must not exceed the UPS's watt rating, which is a separate spec published by the manufacturer. It is often lower than 100W on budget and mid-range units.

The example table below converts each equipment type's watts into a percentage of 85W (the real-power figure at PF 0.85) as a rough steady-state comparison. It assumes the UPS's watt rating is at least 85W; if the manufacturer's watt rating is lower, the comparisons below are optimistic and the real headroom is tighter.

Example Loads (steady-state only)

EquipmentTypical Watts% of 100 VA at PF 0.85
Desktop PC300WPast 85W at PF 0.85
Gaming PC500WPast 85W at PF 0.85
Monitor40W47.06% steady-state
Router + Modem30W35.29% steady-state
Server (inrush-sensitive)500WPast 85W at PF 0.85
NAS (4-bay) (inrush-sensitive)100WPast 85W at PF 0.85
Network Switch (PoE) (inrush-sensitive)150WPast 85W at PF 0.85
LED TV 55"100WPast 85W at PF 0.85

These comparisons use steady-state wattage only. Equipment with large inrush or surge behavior, laser printer fusers, refrigerator and freezer compressors, air conditioners, sump and well pumps, shop motors, and some HVAC blowers, can momentarily draw several times their nameplate watts when they start or cycle. A UPS sized to the steady-state number alone will trip or transfer to battery on those transients. Inductive and motor loads need additional VA headroom beyond the nameplate, and laser printers specifically are usually recommended against on small consumer UPS units. Check the equipment spec sheet for inrush or starting current, or consult the UPS manufacturer's load compatibility notes.

Watts to VA (Reverse)

If you know the watts and need to find the VA rating: VA = Watts ÷ PF. A 85W load at 0.85 PF needs 100 VA minimum.

Current Draw

On an AC circuit, current is set by the apparent power (VA), not the real watts, because VA = V × I by definition. So 100 VA pulls the same amperage regardless of the load's power factor, only the real power delivered (watts) changes with PF.

VoltageCurrent (AC, any PF)Real power at PF 0.85
120V0.8333 A85 W (see details)
240V0.4167 A85 W (see details)

Energy Cost

85W costs $0.01/hour at $0.17/kWh (rates last reviewed April 2026), or $3.47/month (8h/day). Full breakdown.

Common UPS Sizes

How does a 100 VA load compare to standard UPS ratings? The watts columns below convert each UPS's VA rating to a load-side watt figure at two power factors. These are not the UPS's watt ratings. UPS watt ratings are published separately by the manufacturer and are often lower, especially on older and budget units. Use the columns below to compare a load's real power draw to the UPS's VA rating, then check the UPS's spec sheet for its watt rating independently. The use-case column is reference context only; rack and server picks usually need extra VA and PF headroom beyond the steady-state column to absorb inrush at startup and motor-load cycling.

UPS VA RatingLoad watts at PF 0.85Load watts at PF 0.65Typical Use
350 VA297.5W227.5WRouter and cable modem, always-on
500 VA425W325WSingle desktop PC at idle
750 VA637.5W487.5WDesktop PC plus a monitor
1,000 VA850W650WWorkstation with peripherals
1,500 VA1,275W975WSingle rackmount server (plus inrush headroom)
2,200 VA1,870W1,430WTwo or three PCs or a small workgroup
3,000 VA2,550W1,950WSmall server rack (plus inrush and PF headroom)
5,000 VA4,250W3,250WSmall data closet (plus inrush and PF headroom)
10,000 VA8,500W6,500WFull server rack (plus inrush and PF headroom)

Frequently Asked Questions

A load rated at 100 VA draws 85 watts of real power at a power factor of 0.85. At PF 1.0 (resistive) the same 100 VA load draws 100W; at PF 0.65 (computer without PFC) it draws 65W. These are load-side figures, not the watt output of any specific UPS or power supply.
A typical single rackmount server draws 300-500W of real power steady state. A 100 VA UPS covers a load of up to 85W at PF 0.85 on the apparent-power side of the spec, but the UPS's watt rating is a separate spec set by the manufacturer and is often lower than VA × PF. Servers also have inrush on boot (disk spin-up, fan ramp) and short transients under load, so most deployment guidance adds 30-50% headroom on top of the steady-state figure. Always verify (1) the server's nameplate watts and VA, (2) the UPS's published watt rating from the manufacturer's datasheet (not inferred from VA × PF), and (3) the UPS vendor's server sizing guide, rather than relying on a general rule of thumb.
VA includes both real power (watts) and reactive power (VARs). Reactive power does no useful work but still draws current through the conductors. Watts = VA × PF, and PF is bounded between 0 and 1, so a load's watts are never higher than its VA.
No. UPS units publish a VA rating AND a separate watt rating, both set by the manufacturer. The Watts = VA × PF formula converts a load's apparent power to its real power, but the UPS's watt ceiling is an independent spec that is often lower than VA × load PF on budget and older units. A 1000 VA UPS might be rated for 600W real power from one vendor and 1000W from another; you cannot tell from the VA rating alone. Always check the manufacturer's spec sheet for the watt rating and size the load under both ratings independently.
VA = Watts ÷ PF. A 85W load at PF 0.85 has an apparent power of 100 VA, which is what sets the circuit's current draw and what a UPS's VA rating has to cover.
This calculator provides estimates for reference purposes only.