What Is the Voltage Drop for 1/0 AWG at 113A and 125 Feet?

Running 113A through 1/0 AWG copper for 125 feet on a single-phase / DC circuit produces a 3.45-volt drop. On a 120V source that is 2.87%; on 240V it is 1.44%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

1/0 AWG, 113A, 125ft · single-phase / DC
3.45 V drop (2.87% on 120V)
On 120V circuit2.87%
On 240V circuit1.44%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
3.45V (2.87%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 113 × 0.122) ÷ 1000 = 3.45 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.45 ÷ 120) × 100 = 2.87%
On 240V: (3.45 ÷ 240) × 100 = 1.44%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 113A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.6893V0.5744%0.2872%OK
50ft1.38V1.15%0.5744%OK
75ft2.07V1.72%0.8616%OK
100ft2.76V2.3%1.15%OK
150ft4.14V3.45%1.72%Caution
200ft5.51V4.6%2.3%Caution
300ft8.27V6.89%3.45%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 113A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 113A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG3.45V2.87%1.44%OK
2/0 AWG2.73V2.28%1.14%OK
3/0 AWG2.16V1.8%0.9016%OK
4/0 AWG1.72V1.43%0.7157%OK
250 kcmil1.45V1.21%0.6062%OK
300 kcmil1.21V1.01%0.505%OK

Frequently Asked Questions

1/0 AWG carrying 113A over 125ft has a 3.45V drop (2.87% on 120V). Reference: 1.44% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
1/0 AWG already sits within the 3% branch-circuit drop target at these inputs (2.87% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 2.87%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.