What Is the Voltage Drop for 1/0 AWG at 34A and 250 Feet?

1/0 AWG at 34A and 250 feet: 2.07V drop (1.73% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

1/0 AWG, 34A, 250ft · single-phase / DC
2.07 V drop (1.73% on 120V)
On 120V circuit1.73%
On 240V circuit0.8642%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
2.07V (1.73%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 34 × 0.122) ÷ 1000 = 2.07 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.07 ÷ 120) × 100 = 1.73%
On 240V: (2.07 ÷ 240) × 100 = 0.8642%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 34A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2074V0.1728%0.0864%OK
50ft0.4148V0.3457%0.1728%OK
75ft0.6222V0.5185%0.2593%OK
100ft0.8296V0.6913%0.3457%OK
150ft1.24V1.04%0.5185%OK
200ft1.66V1.38%0.6913%OK
300ft2.49V2.07%1.04%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 34A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 34A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG2.07V1.73%0.8642%OK
2/0 AWG1.64V1.37%0.685%OK
3/0 AWG1.3V1.09%0.5426%OK
4/0 AWG1.03V0.8613%0.4307%OK
250 kcmil0.8755V0.7296%0.3648%OK
300 kcmil0.7293V0.6078%0.3039%OK

Frequently Asked Questions

1/0 AWG carrying 34A over 250ft has a 2.07V drop (1.73% on 120V). Reference: 0.8642% on 240V.
On 120V, this run sits at 1.73%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.8642% on 240V versus 1.73% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.