What Is the Voltage Drop for 1/0 AWG at 35A and 100 Feet?

1/0 AWG copper carrying 35 amps over 100 feet on a single-phase / DC circuit drops 0.854 volts (0.7117% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

1/0 AWG, 35A, 100ft · single-phase / DC
0.854 V drop (0.7117% on 120V)
On 120V circuit0.7117%
On 240V circuit0.3558%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
0.85V (0.71%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 100 × 35 × 0.122) ÷ 1000 = 0.854 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.854 ÷ 120) × 100 = 0.7117%
On 240V: (0.854 ÷ 240) × 100 = 0.3558%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 35A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2135V0.1779%0.089%OK
50ft0.427V0.3558%0.1779%OK
75ft0.6405V0.5338%0.2669%OK
100ft0.854V0.7117%0.3558%OK
150ft1.28V1.07%0.5338%OK
200ft1.71V1.42%0.7117%OK
300ft2.56V2.14%1.07%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 35A at 100 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 35A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG0.854V0.7117%0.3558%OK
2/0 AWG0.6769V0.5641%0.282%OK
3/0 AWG0.5362V0.4468%0.2234%OK
4/0 AWG0.4256V0.3547%0.1773%OK
250 kcmil0.3605V0.3004%0.1502%OK
300 kcmil0.3003V0.2503%0.1251%OK

Frequently Asked Questions

1/0 AWG carrying 35A over 100ft has a 0.854V drop (0.7117% on 120V). Reference: 0.3558% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
1/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.7117% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 0.7117%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.3558% on 240V versus 0.7117% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.