What Is the Voltage Drop for 1/0 AWG at 37A and 250 Feet?

1/0 AWG at 37A and 250 feet: 2.26V drop (1.88% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

1/0 AWG, 37A, 250ft · single-phase / DC
2.26 V drop (1.88% on 120V)
On 120V circuit1.88%
On 240V circuit0.9404%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
2.26V (1.88%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 37 × 0.122) ÷ 1000 = 2.26 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.26 ÷ 120) × 100 = 1.88%
On 240V: (2.26 ÷ 240) × 100 = 0.9404%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 37A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2257V0.1881%0.094%OK
50ft0.4514V0.3762%0.1881%OK
75ft0.6771V0.5643%0.2821%OK
100ft0.9028V0.7523%0.3762%OK
150ft1.35V1.13%0.5643%OK
200ft1.81V1.5%0.7523%OK
300ft2.71V2.26%1.13%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 37A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 37A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG2.26V1.88%0.9404%OK
2/0 AWG1.79V1.49%0.7454%OK
3/0 AWG1.42V1.18%0.5905%OK
4/0 AWG1.12V0.9373%0.4687%OK
250 kcmil0.9528V0.794%0.397%OK
300 kcmil0.7937V0.6614%0.3307%OK

Frequently Asked Questions

1/0 AWG carrying 37A over 250ft has a 2.26V drop (1.88% on 120V). Reference: 0.9404% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 1.88%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.9404% on 240V versus 1.88% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.