What Is the Voltage Drop for 1/0 AWG at 41A and 300 Feet?

1/0 AWG at 41A and 300 feet: 3V drop (2.5% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

1/0 AWG, 41A, 300ft · single-phase / DC
3 V drop (2.5% on 120V)
On 120V circuit2.5%
On 240V circuit1.25%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
3.00V (2.50%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 300 × 41 × 0.122) ÷ 1000 = 3 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3 ÷ 120) × 100 = 2.5%
On 240V: (3 ÷ 240) × 100 = 1.25%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 41A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2501V0.2084%0.1042%OK
50ft0.5002V0.4168%0.2084%OK
75ft0.7503V0.6253%0.3126%OK
100ft1V0.8337%0.4168%OK
150ft1.5V1.25%0.6253%OK
200ft2V1.67%0.8337%OK
300ft3V2.5%1.25%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 41A at 300 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 41A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG3V2.5%1.25%OK
2/0 AWG2.38V1.98%0.9912%OK
3/0 AWG1.88V1.57%0.7852%OK
4/0 AWG1.5V1.25%0.6232%OK
250 kcmil1.27V1.06%0.5279%OK
300 kcmil1.06V0.8795%0.4397%OK

Frequently Asked Questions

1/0 AWG carrying 41A over 300ft has a 3V drop (2.5% on 120V). Reference: 1.25% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.25% on 240V versus 2.5% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.5%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.