What Is the Voltage Drop for 1/0 AWG at 48A and 75 Feet?

1/0 AWG copper carrying 48 amps over 75 feet on a single-phase / DC circuit drops 0.8784 volts (0.732% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

1/0 AWG, 48A, 75ft · single-phase / DC
0.8784 V drop (0.732% on 120V)
On 120V circuit0.732%
On 240V circuit0.366%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
0.88V (0.73%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 48 × 0.122) ÷ 1000 = 0.8784 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.8784 ÷ 120) × 100 = 0.732%
On 240V: (0.8784 ÷ 240) × 100 = 0.366%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 48A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2928V0.244%0.122%OK
50ft0.5856V0.488%0.244%OK
75ft0.8784V0.732%0.366%OK
100ft1.17V0.976%0.488%OK
150ft1.76V1.46%0.732%OK
200ft2.34V1.95%0.976%OK
300ft3.51V2.93%1.46%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 48A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 48A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG0.8784V0.732%0.366%OK
2/0 AWG0.6962V0.5802%0.2901%OK
3/0 AWG0.5515V0.4596%0.2298%OK
4/0 AWG0.4378V0.3648%0.1824%OK
250 kcmil0.3708V0.309%0.1545%OK
300 kcmil0.3089V0.2574%0.1287%OK

Frequently Asked Questions

1/0 AWG carrying 48A over 75ft has a 0.8784V drop (0.732% on 120V). Reference: 0.366% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.732%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
1/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.732% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.366% on 240V versus 0.732% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.