What Is the Voltage Drop for 1/0 AWG at 50A and 175 Feet?

1/0 AWG copper carrying 50 amps over 175 feet on a single-phase / DC circuit drops 2.14 volts (1.78% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

1/0 AWG, 50A, 175ft · single-phase / DC
2.14 V drop (1.78% on 120V)
On 120V circuit1.78%
On 240V circuit0.8896%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
2.14V (1.78%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 175 × 50 × 0.122) ÷ 1000 = 2.14 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.14 ÷ 120) × 100 = 1.78%
On 240V: (2.14 ÷ 240) × 100 = 0.8896%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 50A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.305V0.2542%0.1271%OK
50ft0.61V0.5083%0.2542%OK
75ft0.915V0.7625%0.3813%OK
100ft1.22V1.02%0.5083%OK
150ft1.83V1.53%0.7625%OK
200ft2.44V2.03%1.02%OK
300ft3.66V3.05%1.53%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 50A at 175 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 50A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG2.14V1.78%0.8896%OK
2/0 AWG1.69V1.41%0.7051%OK
3/0 AWG1.34V1.12%0.5585%OK
4/0 AWG1.06V0.8867%0.4433%OK
250 kcmil0.9013V0.751%0.3755%OK
300 kcmil0.7508V0.6256%0.3128%OK

Frequently Asked Questions

1/0 AWG carrying 50A over 175ft has a 2.14V drop (1.78% on 120V). Reference: 0.8896% on 240V.
On 120V, this run sits at 1.78%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
Use a larger wire gauge (lower AWG number), shorten the run, or increase the source voltage. Each option reduces the percentage drop, and higher source voltage is usually the most effective change for long runs because the drop is a smaller fraction of a larger reference.
1/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.78% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.