What Is the Voltage Drop for 1/0 AWG at 60A and 25 Feet?

Running 60A through 1/0 AWG copper for 25 feet on a single-phase / DC circuit produces a 0.366-volt drop. On a 120V source that is 0.305%; on 240V it is 0.1525%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

1/0 AWG, 60A, 25ft · single-phase / DC
0.366 V drop (0.305% on 120V)
On 120V circuit0.305%
On 240V circuit0.1525%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
0.37V (0.31%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 60 × 0.122) ÷ 1000 = 0.366 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.366 ÷ 120) × 100 = 0.305%
On 240V: (0.366 ÷ 240) × 100 = 0.1525%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 60A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.366V0.305%0.1525%OK
50ft0.732V0.61%0.305%OK
75ft1.1V0.915%0.4575%OK
100ft1.46V1.22%0.61%OK
150ft2.2V1.83%0.915%OK
200ft2.93V2.44%1.22%OK
300ft4.39V3.66%1.83%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 60A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 60A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG0.366V0.305%0.1525%OK
2/0 AWG0.2901V0.2418%0.1209%OK
3/0 AWG0.2298V0.1915%0.0958%OK
4/0 AWG0.1824V0.152%0.076%OK
250 kcmil0.1545V0.1288%0.0644%OK
300 kcmil0.1287V0.1072%0.0536%OK

Frequently Asked Questions

1/0 AWG carrying 60A over 25ft has a 0.366V drop (0.305% on 120V). Reference: 0.1525% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
1/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.305% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.305%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.