What Is the Voltage Drop for 1/0 AWG at 60A and 75 Feet?

1/0 AWG copper carrying 60 amps over 75 feet on a single-phase / DC circuit drops 1.1 volts (0.915% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

1/0 AWG, 60A, 75ft · single-phase / DC
1.1 V drop (0.915% on 120V)
On 120V circuit0.915%
On 240V circuit0.4575%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
1.10V (0.92%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 60 × 0.122) ÷ 1000 = 1.1 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.1 ÷ 120) × 100 = 0.915%
On 240V: (1.1 ÷ 240) × 100 = 0.4575%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 60A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.366V0.305%0.1525%OK
50ft0.732V0.61%0.305%OK
75ft1.1V0.915%0.4575%OK
100ft1.46V1.22%0.61%OK
150ft2.2V1.83%0.915%OK
200ft2.93V2.44%1.22%OK
300ft4.39V3.66%1.83%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 60A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 60A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG1.1V0.915%0.4575%OK
2/0 AWG0.8703V0.7253%0.3626%OK
3/0 AWG0.6894V0.5745%0.2873%OK
4/0 AWG0.5472V0.456%0.228%OK
250 kcmil0.4635V0.3863%0.1931%OK
300 kcmil0.3861V0.3218%0.1609%OK

Frequently Asked Questions

1/0 AWG carrying 60A over 75ft has a 1.1V drop (0.915% on 120V). Reference: 0.4575% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
1/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.915% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 0.915%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.4575% on 240V versus 0.915% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.