What Is the Voltage Drop for 1/0 AWG at 74A and 200 Feet?

Running 74A through 1/0 AWG copper for 200 feet on a single-phase / DC circuit produces a 3.61-volt drop. On a 120V source that is 3.01%; on 240V it is 1.5%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

1/0 AWG, 74A, 200ft · single-phase / DC
3.61 V drop (3.01% on 120V)
On 120V circuit3.01%
On 240V circuit1.5%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
3.61V (3.01%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 200 × 74 × 0.122) ÷ 1000 = 3.61 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.61 ÷ 120) × 100 = 3.01%
On 240V: (3.61 ÷ 240) × 100 = 1.5%

How This Estimate Changes with Run Length and Gauge

Gauge That Meets the 3% Target

The smallest gauge in our table that clears the 3% drop target at 74A over 200ft on 120V is 2/0 AWG. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 74A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.4514V0.3762%0.1881%OK
50ft0.9028V0.7523%0.3762%OK
75ft1.35V1.13%0.5643%OK
100ft1.81V1.5%0.7523%OK
150ft2.71V2.26%1.13%OK
200ft3.61V3.01%1.5%Caution
300ft5.42V4.51%2.26%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 74A at 200 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 74A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG3.61V3.01%1.5%Caution
2/0 AWG2.86V2.39%1.19%OK
3/0 AWG2.27V1.89%0.9447%OK
4/0 AWG1.8V1.5%0.7499%OK
250 kcmil1.52V1.27%0.6352%OK
300 kcmil1.27V1.06%0.5291%OK

Frequently Asked Questions

1/0 AWG carrying 74A over 200ft has a 3.61V drop (3.01% on 120V). Reference: 1.5% on 240V.
Yes. Aluminum has roughly 1.3 to 1.4 times the resistance of copper at the NEC Chapter 9 Table 8 75°C reference temperature, so for the same voltage drop an aluminum conductor is typically one to two gauges larger than copper. The exact gap depends on whether ampacity or voltage drop is binding, and the install still needs anti-oxidant compound and aluminum-rated lugs.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.5% on 240V versus 3.01% on 120V.
Use a larger wire gauge (lower AWG number), shorten the run, or increase the source voltage. Each option reduces the percentage drop, and higher source voltage is usually the most effective change for long runs because the drop is a smaller fraction of a larger reference.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.