What Is the Voltage Drop for 1/0 AWG at 82A and 25 Feet?
1/0 AWG at 82A and 25 feet: 0.5002V drop (0.4168% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.
1/0 AWG, 82A, 25ft · single-phase / DC
0.5002 V drop (0.4168% on 120V)
On 120V circuit0.4168%
On 240V circuit0.2084%
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Voltage drop is proportional to distance. Here is 1/0 AWG at 82A at different distances:
Distance
Drop (V)
% on 120V
% on 240V
NEC (120V)
25ft
0.5002V
0.4168%
0.2084%
OK
50ft
1V
0.8337%
0.4168%
OK
75ft
1.5V
1.25%
0.6253%
OK
100ft
2V
1.67%
0.8337%
OK
150ft
3V
2.5%
1.25%
OK
200ft
4V
3.33%
1.67%
Caution
300ft
6V
5%
2.5%
Past 5%
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 82A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 82A load are listed, since thinner gauges would fail the ampacity check before drop even matters.
1/0 AWG carrying 82A over 25ft has a 0.5002V drop (0.4168% on 120V). Reference: 0.2084% on 240V.
Yes. Aluminum has roughly 1.3 to 1.4 times the resistance of copper at the NEC Chapter 9 Table 8 75°C reference temperature, so for the same voltage drop an aluminum conductor is typically one to two gauges larger than copper. The exact gap depends on whether ampacity or voltage drop is binding, and the install still needs anti-oxidant compound and aluminum-rated lugs.
Use a larger wire gauge (lower AWG number), shorten the run, or increase the source voltage. Each option reduces the percentage drop, and higher source voltage is usually the most effective change for long runs because the drop is a smaller fraction of a larger reference.
1/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.4168% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.