What Is the Voltage Drop for 1/0 AWG at 8A and 500 Feet?

Running 8A through 1/0 AWG copper for 500 feet on a single-phase / DC circuit produces a 0.976-volt drop. On a 120V source that is 0.8133%; on 240V it is 0.4067%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

1/0 AWG, 8A, 500ft · single-phase / DC
0.976 V drop (0.8133% on 120V)
On 120V circuit0.8133%
On 240V circuit0.4067%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
0.98V (0.81%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 500 × 8 × 0.122) ÷ 1000 = 0.976 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.976 ÷ 120) × 100 = 0.8133%
On 240V: (0.976 ÷ 240) × 100 = 0.4067%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 8A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0488V0.0407%0.0203%OK
50ft0.0976V0.0813%0.0407%OK
75ft0.1464V0.122%0.061%OK
100ft0.1952V0.1627%0.0813%OK
150ft0.2928V0.244%0.122%OK
200ft0.3904V0.3253%0.1627%OK
300ft0.5856V0.488%0.244%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 8A at 500 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 8A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG0.976V0.8133%0.4067%OK
2/0 AWG0.7736V0.6447%0.3223%OK
3/0 AWG0.6128V0.5107%0.2553%OK
4/0 AWG0.4864V0.4053%0.2027%OK
250 kcmil0.412V0.3433%0.1717%OK
300 kcmil0.3432V0.286%0.143%OK

Frequently Asked Questions

1/0 AWG carrying 8A over 500ft has a 0.976V drop (0.8133% on 120V). Reference: 0.4067% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.4067% on 240V versus 0.8133% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.8133%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.