What Is the Voltage Drop for 1/0 AWG at 96A and 25 Feet?

Running 96A through 1/0 AWG copper for 25 feet on a single-phase / DC circuit produces a 0.5856-volt drop. On a 120V source that is 0.488%; on 240V it is 0.244%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

1/0 AWG, 96A, 25ft · single-phase / DC
0.5856 V drop (0.488% on 120V)
On 120V circuit0.488%
On 240V circuit0.244%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1/0 AWG
0.59V (0.49%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 96 × 0.122) ÷ 1000 = 0.5856 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.5856 ÷ 120) × 100 = 0.488%
On 240V: (0.5856 ÷ 240) × 100 = 0.244%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1/0 AWG at 96A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.5856V0.488%0.244%OK
50ft1.17V0.976%0.488%OK
75ft1.76V1.46%0.732%OK
100ft2.34V1.95%0.976%OK
150ft3.51V2.93%1.46%OK
200ft4.68V3.9%1.95%Caution
300ft7.03V5.86%2.93%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 96A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 96A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1/0 AWG0.5856V0.488%0.244%OK
2/0 AWG0.4642V0.3868%0.1934%OK
3/0 AWG0.3677V0.3064%0.1532%OK
4/0 AWG0.2918V0.2432%0.1216%OK
250 kcmil0.2472V0.206%0.103%OK
300 kcmil0.2059V0.1716%0.0858%OK

Frequently Asked Questions

1/0 AWG carrying 96A over 25ft has a 0.5856V drop (0.488% on 120V). Reference: 0.244% on 240V.
On 120V, this run sits at 0.488%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.244% on 240V versus 0.488% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.