What Is the Voltage Drop for 10 AWG at 6A and 250 Feet?

Running 6A through 10 AWG copper for 250 feet on a single-phase / DC circuit produces a 3.72-volt drop. On a 120V source that is 3.1%; on 240V it is 1.55%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

10 AWG, 6A, 250ft · single-phase / DC
3.72 V drop (3.1% on 120V)
On 120V circuit3.1%
On 240V circuit1.55%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

10 AWG
3.72V (3.10%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 6 × 1.24) ÷ 1000 = 3.72 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.72 ÷ 120) × 100 = 3.1%
On 240V: (3.72 ÷ 240) × 100 = 1.55%

How This Estimate Changes with Run Length and Gauge

Gauge That Meets the 3% Target

The smallest gauge in our table that clears the 3% drop target at 6A over 250ft on 120V is 8 AWG. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.

Impact of Distance

Voltage drop is proportional to distance. Here is 10 AWG at 6A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.372V0.31%0.155%OK
50ft0.744V0.62%0.31%OK
75ft1.12V0.93%0.465%OK
100ft1.49V1.24%0.62%OK
150ft2.23V1.86%0.93%OK
200ft2.98V2.48%1.24%OK
300ft4.46V3.72%1.86%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 6A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 6A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
10 AWG3.72V3.1%1.55%Caution
8 AWG2.33V1.95%0.9725%OK
6 AWG1.47V1.23%0.6138%OK
4 AWG0.924V0.77%0.385%OK
3 AWG0.735V0.6125%0.3063%OK
2 AWG0.582V0.485%0.2425%OK

Frequently Asked Questions

10 AWG carrying 6A over 250ft has a 3.72V drop (3.1% on 120V). Reference: 1.55% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 3.1%, which is past the 3% branch target; within the 5% feeder+branch total. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.55% on 240V versus 3.1% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.