What Is the Voltage Drop for 10 AWG at 7A and 50 Feet?
10 AWG copper carrying 7 amps over 50 feet on a single-phase / DC circuit drops 0.868 volts (0.7233% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.
10 AWG, 7A, 50ft · single-phase / DC
0.868 V drop (0.7233% on 120V)
On 120V circuit0.7233%
On 240V circuit0.3617%
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Voltage drop is proportional to distance. Here is 10 AWG at 7A at different distances:
Distance
Drop (V)
% on 120V
% on 240V
NEC (120V)
25ft
0.434V
0.3617%
0.1808%
OK
50ft
0.868V
0.7233%
0.3617%
OK
75ft
1.3V
1.09%
0.5425%
OK
100ft
1.74V
1.45%
0.7233%
OK
150ft
2.6V
2.17%
1.09%
OK
200ft
3.47V
2.89%
1.45%
OK
300ft
5.21V
4.34%
2.17%
Caution
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 7A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 7A load are listed, since thinner gauges would fail the ampacity check before drop even matters.
10 AWG carrying 7A over 50ft has a 0.868V drop (0.7233% on 120V). Reference: 0.3617% on 240V.
On 120V, this run sits at 0.7233%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Yes. Aluminum has roughly 1.3 to 1.4 times the resistance of copper at the NEC Chapter 9 Table 8 75°C reference temperature, so for the same voltage drop an aluminum conductor is typically one to two gauges larger than copper. The exact gap depends on whether ampacity or voltage drop is binding, and the install still needs anti-oxidant compound and aluminum-rated lugs.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
10 AWG already sits within the 3% branch-circuit drop target at these inputs (0.7233% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.