What Is the Voltage Drop for 12 AWG at 11A and 75 Feet?

12 AWG at 11A and 75 feet: 3.27V drop (2.72% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

12 AWG, 11A, 75ft · single-phase / DC
3.27 V drop (2.72% on 120V)
On 120V circuit2.72%
On 240V circuit1.36%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

12 AWG
3.27V (2.72%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 11 × 1.98) ÷ 1000 = 3.27 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.27 ÷ 120) × 100 = 2.72%
On 240V: (3.27 ÷ 240) × 100 = 1.36%

How This Estimate Changes with Run Length and Gauge

Gauge Check

12 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 12 AWG at 11A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft1.09V0.9075%0.4538%OK
50ft2.18V1.82%0.9075%OK
75ft3.27V2.72%1.36%OK
100ft4.36V3.63%1.82%Caution
150ft6.53V5.45%2.72%Past 5%
200ft8.71V7.26%3.63%Past 5%
300ft13.07V10.89%5.45%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 11A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 11A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
12 AWG3.27V2.72%1.36%OK
10 AWG2.05V1.7%0.8525%OK
8 AWG1.28V1.07%0.5349%OK
6 AWG0.8101V0.6751%0.3376%OK
4 AWG0.5082V0.4235%0.2118%OK
3 AWG0.4043V0.3369%0.1684%OK

Frequently Asked Questions

12 AWG carrying 11A over 75ft has a 3.27V drop (2.72% on 120V). Reference: 1.36% on 240V.
On 120V, this run sits at 2.72%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
12 AWG already sits within the 3% branch-circuit drop target at these inputs (2.72% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Use a larger wire gauge (lower AWG number), shorten the run, or increase the source voltage. Each option reduces the percentage drop, and higher source voltage is usually the most effective change for long runs because the drop is a smaller fraction of a larger reference.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.