What Is the Voltage Drop for 12 AWG at 14A and 50 Feet?
Running 14A through 12 AWG copper for 50 feet on a single-phase / DC circuit produces a 2.77-volt drop. On a 120V source that is 2.31%; on 240V it is 1.16%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge Check
12 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.
Impact of Distance
Voltage drop is proportional to distance. Here is 12 AWG at 14A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 1.39V | 1.16% | 0.5775% | OK |
| 50ft | 2.77V | 2.31% | 1.16% | OK |
| 75ft | 4.16V | 3.47% | 1.73% | Caution |
| 100ft | 5.54V | 4.62% | 2.31% | Caution |
| 150ft | 8.32V | 6.93% | 3.47% | Past 5% |
| 200ft | 11.09V | 9.24% | 4.62% | Past 5% |
| 300ft | 16.63V | 13.86% | 6.93% | Past 5% |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 14A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 14A load are listed, since thinner gauges would fail the ampacity check before drop even matters.