What Is the Voltage Drop for 12 AWG at 19A and 25 Feet?
12 AWG at 19A and 25 feet: 1.88V drop (1.57% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge Check
12 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.
Impact of Distance
Voltage drop is proportional to distance. Here is 12 AWG at 19A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 1.88V | 1.57% | 0.7838% | OK |
| 50ft | 3.76V | 3.14% | 1.57% | Caution |
| 75ft | 5.64V | 4.7% | 2.35% | Caution |
| 100ft | 7.52V | 6.27% | 3.14% | Past 5% |
| 150ft | 11.29V | 9.41% | 4.7% | Past 5% |
| 200ft | 15.05V | 12.54% | 6.27% | Past 5% |
| 300ft | 22.57V | 18.81% | 9.41% | Past 5% |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 19A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 19A load are listed, since thinner gauges would fail the ampacity check before drop even matters.