12 AWG at 25A and 200 Feet: Ampacity-Invalid Reference Calculation

Reference voltage-drop calculation only. 12 AWG is NEC-capped at 20A branch-circuit OCP per NEC 240.4(D) (75°C ampacity 25A), so 25A on this gauge fails the ampacity check before voltage drop ever enters the conversation. Do not use the number below as an install spec. As a load-side reference, 12 AWG copper at 25 amps over 200 feet on a single-phase / DC circuit would drop 19.8 volts (16.5% on 120V, 8.25% on 240V).

12 AWG, 25A, 200ft · single-phase / DC · reference only, ampacity-invalid
19.8 V drop (16.5% on 120V)
On 120V circuit16.5%
On 240V circuit8.25%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

12 AWG
19.80V (16.50%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 200 × 25 × 1.98) ÷ 1000 = 19.8 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (19.8 ÷ 120) × 100 = 16.5%
On 240V: (19.8 ÷ 240) × 100 = 8.25%

How This Estimate Changes with Run Length and Gauge

Gauge That Meets the 3% Target

12 AWG can't carry the 25A load in the first place, its branch-circuit OCP cap is 20A under typical conditions. The smallest gauge in our table that clears both the ampacity cap and the 3% drop target at these inputs is 4 AWG. Run the full wire-size calculator for run length, material, and drop-target variations.

Impact of Distance

Voltage drop is proportional to distance. Here is 12 AWG at 25A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft2.48V2.06%1.03%OK
50ft4.95V4.13%2.06%Caution
75ft7.43V6.19%3.09%Past 5%
100ft9.9V8.25%4.13%Past 5%
150ft14.85V12.38%6.19%Past 5%
200ft19.8V16.5%8.25%Past 5%
300ft29.7V24.75%12.38%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 25A at 200 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 25A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
10 AWG12.4V10.33%5.17%Past 5%
8 AWG7.78V6.48%3.24%Past 5%
6 AWG4.91V4.09%2.05%Caution
4 AWG3.08V2.57%1.28%OK
3 AWG2.45V2.04%1.02%OK
2 AWG1.94V1.62%0.8083%OK
1 AWG1.54V1.28%0.6417%OK
1/0 AWG1.22V1.02%0.5083%OK
2/0 AWG0.967V0.8058%0.4029%OK
3/0 AWG0.766V0.6383%0.3192%OK
4/0 AWG0.608V0.5067%0.2533%OK
250 kcmil0.515V0.4292%0.2146%OK
300 kcmil0.429V0.3575%0.1788%OK
350 kcmil0.367V0.3058%0.1529%OK
500 kcmil0.258V0.215%0.1075%OK
750 kcmil0.171V0.1425%0.0713%OK

Frequently Asked Questions

12 AWG carrying 25A over 200ft has a 19.8V drop (16.5% on 120V), but 12 AWG is NEC-capped at 20A branch-circuit OCP per NEC 240.4(D), so 25A on 12 AWG is ampacity-invalid and the drop figure above is a reference calculation only, not an install spec. Reference: 8.25% on 240V.
This run is at 16.5% on 120V, past the 3% branch-circuit drop target. If you want to land under 3% at 25A over 200ft on 120V, the smallest gauge in our table that clears it is 4 AWG at 2.57%. Going up one size from 12 AWG is not always enough, each AWG step only drops the resistance by roughly 20-25%, so on long runs or high currents you often have to skip one or two sizes to meet the target. NEC 210.19(A) Informational Note 4 frames 3% as a recommendation, not a code requirement, so the right answer for you also depends on the load (motor startup, sensitive electronics) and how much drop is tolerable.
Use a larger wire gauge (lower AWG number), shorten the run, or increase the source voltage. Each option reduces the percentage drop, and higher source voltage is usually the most effective change for long runs because the drop is a smaller fraction of a larger reference.
On 120V, this run sits at 16.5%, which is past both the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements. However, 12 AWG is ampacity-invalid for 25A (NEC 240.4(D) caps 12 AWG at 20A branch-circuit OCP), so this is a reference drop calculation only and the 3% check does not make this a valid install.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.