What Is the Voltage Drop for 12 AWG at 8A and 125 Feet?
Running 8A through 12 AWG copper for 125 feet on a single-phase / DC circuit produces a 3.96-volt drop. On a 120V source that is 3.3%; on 240V it is 1.65%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge That Meets the 3% Target
The smallest gauge in our table that clears the 3% drop target at 8A over 125ft on 120V is 10 AWG. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.
Impact of Distance
Voltage drop is proportional to distance. Here is 12 AWG at 8A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 0.792V | 0.66% | 0.33% | OK |
| 50ft | 1.58V | 1.32% | 0.66% | OK |
| 75ft | 2.38V | 1.98% | 0.99% | OK |
| 100ft | 3.17V | 2.64% | 1.32% | OK |
| 150ft | 4.75V | 3.96% | 1.98% | Caution |
| 200ft | 6.34V | 5.28% | 2.64% | Past 5% |
| 300ft | 9.5V | 7.92% | 3.96% | Past 5% |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 8A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 8A load are listed, since thinner gauges would fail the ampacity check before drop even matters.