What Is the Voltage Drop for 1 AWG at 114A and 25 Feet?

Running 114A through 1 AWG copper for 25 feet on a single-phase / DC circuit produces a 0.8778-volt drop. On a 120V source that is 0.7315%; on 240V it is 0.3657%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

1 AWG, 114A, 25ft · single-phase / DC
0.8778 V drop (0.7315% on 120V)
On 120V circuit0.7315%
On 240V circuit0.3657%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
0.88V (0.73%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 114 × 0.154) ÷ 1000 = 0.8778 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.8778 ÷ 120) × 100 = 0.7315%
On 240V: (0.8778 ÷ 240) × 100 = 0.3657%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 114A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.8778V0.7315%0.3657%OK
50ft1.76V1.46%0.7315%OK
75ft2.63V2.19%1.1%OK
100ft3.51V2.93%1.46%OK
150ft5.27V4.39%2.19%Caution
200ft7.02V5.85%2.93%Past 5%
300ft10.53V8.78%4.39%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 114A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 114A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG0.8778V0.7315%0.3657%OK
1/0 AWG0.6954V0.5795%0.2898%OK
2/0 AWG0.5512V0.4593%0.2297%OK
3/0 AWG0.4366V0.3639%0.1819%OK
4/0 AWG0.3466V0.2888%0.1444%OK
250 kcmil0.2936V0.2446%0.1223%OK

Frequently Asked Questions

1 AWG carrying 114A over 25ft has a 0.8778V drop (0.7315% on 120V). Reference: 0.3657% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.7315%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.3657% on 240V versus 0.7315% on 120V.
1 AWG already sits within the 3% branch-circuit drop target at these inputs (0.7315% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.