What Is the Voltage Drop for 1 AWG at 121A and 50 Feet?
1 AWG copper carrying 121 amps over 50 feet on a single-phase / DC circuit drops 1.86 volts (1.55% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge Check
1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.
Impact of Distance
Voltage drop is proportional to distance. Here is 1 AWG at 121A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 0.9317V | 0.7764% | 0.3882% | OK |
| 50ft | 1.86V | 1.55% | 0.7764% | OK |
| 75ft | 2.8V | 2.33% | 1.16% | OK |
| 100ft | 3.73V | 3.11% | 1.55% | Caution |
| 150ft | 5.59V | 4.66% | 2.33% | Caution |
| 200ft | 7.45V | 6.21% | 3.11% | Past 5% |
| 300ft | 11.18V | 9.32% | 4.66% | Past 5% |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 121A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 121A load are listed, since thinner gauges would fail the ampacity check before drop even matters.