What Is the Voltage Drop for 1 AWG at 125A and 75 Feet?

1 AWG at 125A and 75 feet: 2.89V drop (2.41% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

1 AWG, 125A, 75ft · single-phase / DC
2.89 V drop (2.41% on 120V)
On 120V circuit2.41%
On 240V circuit1.2%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

1 AWG
2.89V (2.41%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 125 × 0.154) ÷ 1000 = 2.89 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.89 ÷ 120) × 100 = 2.41%
On 240V: (2.89 ÷ 240) × 100 = 1.2%

How This Estimate Changes with Run Length and Gauge

Gauge Check

1 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 1 AWG at 125A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.9625V0.8021%0.401%OK
50ft1.93V1.6%0.8021%OK
75ft2.89V2.41%1.2%OK
100ft3.85V3.21%1.6%Caution
150ft5.78V4.81%2.41%Caution
200ft7.7V6.42%3.21%Past 5%
300ft11.55V9.63%4.81%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 125A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 125A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
1 AWG2.89V2.41%1.2%OK
1/0 AWG2.29V1.91%0.9531%OK
2/0 AWG1.81V1.51%0.7555%OK
3/0 AWG1.44V1.2%0.5984%OK
4/0 AWG1.14V0.95%0.475%OK
250 kcmil0.9656V0.8047%0.4023%OK

Frequently Asked Questions

1 AWG carrying 125A over 75ft has a 2.89V drop (2.41% on 120V). Reference: 1.2% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.2% on 240V versus 2.41% on 120V.
On 120V, this run sits at 2.41%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
1 AWG already sits within the 3% branch-circuit drop target at these inputs (2.41% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.